Declaration of Conformity: Invertek Drives Ltd hereby states that the Optidrive E2 product range is CE marked for the low voltage directive and conforms to the following harmonised European directives: EN 61800-5-1: 2003 Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
The emissions limits defined by EN61800-3 cat C3 (2 environment) are upheld for screened cable lengths of up to 25m. The cable screen should be connected to earth on both the drive and motor sides. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
2. General Information and Ratings This chapter contains information about the Optidrive E2 including how to identify the drive 2.1. Identifying the drive by model number Each drive can be identified by its model number, as shown in Figure 1 Drive Model Number Format. The model number is on the shipping label and the drive nameplate.
Note: Dimension Z assumes that the drives are mounted side-by-side with no clearance. Typical drive heat losses are 3% of operating load conditions. Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Grounding the Drive This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated equipment.
The drive has been designed to operate with Permanent Split Capacitor motors (Cap run) or Shaded Pole motors. Invertek Drives recommends that you refer to the motor manufacturer’s wiring guidelines if reverse rotation of the motor is required. Optidrive E2 Single Phase Output User Guide...
When in Keypad mode is used to Stop a running drive. When in keypad mode, used to Start a stopped drive or START to reverse the direction of rotation if bi-directional keypad mode is enabled Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Pressing the key will start the drive accelerating through the boost starting cycle then to the target speed. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Code 0 to 9 999 access Change code in P-39 to prevent unauthorised access to the Extended Parameter Set NOTE Default parameter values for Horse Power rated drives are shown in brackets Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
(25s between attempts). If fault has cleared drive will restart. To reset the counter the Drive must be powered down, reset on the keypad or by re- enabling the drive. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Page 13
4..20mA, r 4..20mA, 0 ..10V when drive is enabled. format t 20..4mA r 20..4mA “r” indicates the drive will ramp to Preset Speed 1 if signal is removed when drive is enabled Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Drive serial number 000000 … 999999 Unique drive serial number P00-19 00-000 … 99-999 e.g. 540102 / 32 / 005 Drive identifier Drive rating, drive type P00-20 Drive rating e.g. 0.37, 1 230,1P-out Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
24), provided P-05=0 Open: Fast Stop Open: Stop (disable) Open : Analog speed ref Analog input 1 (disable) Closed: Run (enable) Closed : Preset speed 1 reference Closed: Run (enable) Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable the drive when the enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
The analog reference used for PI controller can also be used as the local speed reference when P15=1. Further information on configuring the PI controller for typical feedback applications; please refer to the Application Note AN-ODE-02 or Advanced User Guide. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
IP20 is -10 … 50°C (frost and condensation free) IP55/NEMA 12 is -10 … 40°C (frost and condensation free) Storage ambient temperature range: -40 … 60°C Maximum altitude: 2000m. Derate above 1000m : 1% / 100m Maximum humidity: 95%, non-condensing Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above specified maximum short-circuit Amperes symmetrical with the specified maximum supply voltage. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
This gives adequate ventilation space between drives. If the IP55 Optidrive is to be installed above another drive or any other heat-producing device, the minimum vertical spacing is 150mm (5.9 inches) Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
On the switched models the main power isolator switch can be locked in the ‘Off’ position using a 20mm standard shackle padlock (not supplied). 11.4. Removing the Terminal Cover To access the connection terminals, the drive front cover needs to be removed as shown below. Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Run in Hand STOP Run in Auto (P-20) Auto – Speed Reference from Modbus NOTE To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101) Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...
Page 24
Optidrive E2 Single Phase Output User Guide www.invertek.co.uk...