Basic Function Group: F0.00-F0.27 - Powtran PI500-E Series Manual

Table of Contents

Advertisement

Displays AB phase pulse count of the current ABZ or UVW encoder
d0.34
Z signal counter
Displays Z phase pulse count of the current ABZ or UVW encoder
d0.35
Inverter status
Displays inverter running status information Data definition format is as follows:
Bit0
Bit1
Bit2
Bit3
Bit4
Inverter type
d0.36
1.G type (constant torque load type); 2.F type (fans/pumps load type)
d0.37
AI1 voltage before correction
d0.38
AI2 voltage before correction
d0.39
Panel potentiometer voltage before correction
d0.40
Reserve
d0.41
motor temperature inspection function3
Motor temperature sensor signal,need connect to control board S1 S2 GND terminal,

5-2-2.Basic function group: F0.00-F0.27

Code
Parameter name
F0.00 Motor control mode
0:Vector control without PG
Refers to the open-loop vector control for high-performance control applications typically ,
only one inverter to drive a motor.
1: Vector control with PG
Refers to the closed-loop vector control, motor encoder client must be installed , the drive
must be matching with the same type of PG encoder card . Suitable for high-precision speed
control or torque control . An inverter can drive only one motor.
2:V/F control
Suitable for less precision control applications, such as fan and pump loads .Oneinverter can
be used for several motors at the same time.
Note:When vector control mode , the drive andmotor capacity can not be vary widely.The
drive‟s power can be bigger than motor‟s power two degree or smaller than motor‟s power one
degree.If not, it may result in not very good performancecontrol , or the drive system does not
work normally .
F0.01 Keyboard set frequency 0.00Hz to F0.19(maximum frequency)
When "Digital Setting" or "Terminal UP/DOWN " is selected as frequency source, the
parameter value is the initial value of the inverter frequency digital setting.
Frequenc y command
F0.02
resolution
0: stop; 1: forward; 2: reverse
0: constant; 1: acceleration; 2: deceleration
0: bus voltage normal; 1: undervoltage
Setting range
Vector control without PG
Vector control with PG
V/F control
0.1Hz
0.01Hz
57
Chapter 5 Function parameter
Factory
setting
0
1
0
2
50.00Hz ☆
1
2
2
-
-
0.01V
0.01V
0.01V
0℃
Chan
ge
Limit