Mounting the Inverter

The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a
noncombustible surface*. This surface and the mounting hardware must also be capable of
supporting at least twice the weight of the inverter. To meet regulatory requirements, the MS-G
Series must be mounted in one of the following positions as shown in Figure 2-3:
above or under a horizontal surface (shelf or table),
on a vertical surface (wall) with the DC terminals to the right,
on a vertical surface (wall) with the DC terminals toward the bottom, the MP-HOOD (inverter
hood) installed on the top, and either the ME-CB or MPX-CB (Conduit box), or the MMP series
(single inverter enclosure) installed on the inverter's bottom.
Info: The ME-CB, MPX-CB, and MMP Series enclosures prevent material from falling
out the bottom in the event of an internal fi re, and also allow suffi cient ventilation to
prevent the inverter from overheating under normal operating conditions. The MP-
HOOD inverter hood prevents items from falling inside causing damage to the inverter.
Info: Sensata provides a backplate for mounting the inverter. These backplates also
provide the ability to mount the MMP Series enclosure (PN: BP-MMP).
After determining the mounting position, refer to the physical dimensions as shown in Figures
2-4 or 2-5, or use the base of the inverter as a template to mark your mounting screw locations.
After marking the mounting screw locations, mount the unit with appropriate mounting hardware.
* Noncombustible surface – A surface made of material that will not ignite, burn, support combustion, or
release fl ammable vapors when subjected to fi re or heat as per the ASTM E136 standard. For the most part,
these are materials that are largely comprised of inorganic materials such as stone, steel, iron, brick, tile,
concrete, slate, and glass. Avoid common building materials such as gypsum board as well as any paint, wall
coverings, and all types of wood.
20
30
30
S
HELF OR
M
(
RIGHT SIDE UP
W
ALL
(DC
TERMINALS TO THE RIGHT
© 2015 Sensata Technologies
T
ABLE
OUNTED
)
M
OUNTED
)

Figure 2-3, Approved Mounting Positions

S
T
M
HELF OR
ABLE
OUNTED
(
)
UP SIDE DOWN
Installation
W
M
ALL
OUNTED
(DC
TERMINALS
*)
FACING DOWN
*W
HEN THE INVERTER
IS MOUNTED ON THE
,
WALL IN THIS POSITION
THE INVERTER HOOD
(MP-HOOD)
MUST
BE MOUNTED OVER THE
(
);
EXHAUST VENTS
TOP
AND EITHER A CONDUIT
(ME-CB
BOX
OR
MPX-CB)
MMP
OR
S
ERIES ENCLOSURE MUST
BE ATTACHED TO THE
'
DC
INVERTER
S
END
(
).
BOTTOM
Page 10

Advertisement

Table of Contents
loading

Table of Contents