Battery Safety Information:
WARNING: Working in the vicinity of lead-acid batteries is dangerous. There is a risk of acid
exposure.
WARNING: Batteries generate explosive gases during operation.
WARNING: There is risk of high current discharge from shorting a battery that can cause fire
and explosion. Use insulated tools during installation.
WARNING: Remove all rings, watches, jewelry or other conductive items before working near
the batteries.
WARNING: Inspect the batteries once a year for cracks, leaks or swelling.
WARNING: Dispose of the batteries according to local regulations. Do not incinerate
batteries; risk of explosion exists.
THEORY OF OPERATION
The "Local On/Off Switch" located on front, or the "Remote On/Off Switch" if used controls the
inverter. Both the Local and "Remote On/Off" switches are configured in series. To control the
inverter remotely set the "Local On/Off switch" to ON.
The inverter will operate in "inverter mode" only.

Inverter Power Mode

When the inverter is in "Inverter Power" mode, the green LED "Inverter" will come on. The AC
power produced by the inverter comes from the energy stored in the battery bank through a
sophisticated electronic inversion process. A transformer, a Metal Oxide Silicon Field Effect
Transistors (MOSFET), a filter capacitor and a waveform stabilizer circuit are used to generate
clean useful AC power.
Note: The signal output waveform produced by the inverter when in "inverter mode" is pure
sinusoidal. It has a total harmonic distortion of less than 5%.