Status and troubleshooting via LED

10
In the event of failure/error of the MotorController one or more diodes will light and/or blink.
On the WCC 103 there are 3 diodes - 2 green and 1 yellow - that can indicate errors on the MotorController.
Irrespective which diode lights or blinks, the indicator is based on a 3.2 second sequence that is repeated continuously. Each
sequence is defined by 32 x 0.1 second time segments.
If there are several errors on the MotorController simultaneously they are displayed by priority, i.e. error messages for the most
critical failures are shown first and repeated until the failure is remedied. Then error number two is shown, which likewise is
repeated until the error is remedied etc. The following overview shows the most frequently occurring errors, if an error other than
those listed below is indicated, contact WindowMaster.
Yellow diode – LED 1
If the yellow diode lights, this indicates an error on the MotorController.
Black = diode off
Error indicator on the yellow diode is a total errors indicator. Detailed information on the error type can be decoded on the green
diode.
Green diode – LED 2
If the green diode LED 2 (closest to X10) blinks, this indicates the error on the MotorController.
Black = diode off
Green diode – LED 4
The green diode LED 4 (furthest from X10) indicates status of or error on the motor line.
Black = diode off

Commissioning and test run

11
In the event of error messages, refer to chapter "Status and troubleshooting via LED".
11.1

MotorController fully installed, without operating power

a.
Check all mechanical and electrical components for damage.
b.
Check all screw and plug connections for tightness and/or firm seating.
c.
Check that all external components are installed; check polarity for the ±24V actuators
11.2

With network power

Adhere to the relevant regulations!
Connect the mains cables and reapply the mains voltage.
11.3

Comfort keypad

Look closely at the actuators as they open and close - there must not be any obstacles in any position and the actuator connection
wires must not be overstrained with pulling or pinching.
Test every single comfort keypad.