Example For Mintime/Maxtime Logic - netvox R718KA2 User Manual

Wireless 2-input ma current meter interface, 4~20 ma
Hide thumbs Also See for R718KA2:
Table of Contents

Advertisement

Description
Device
Config
ReportReq
Config
ReportRsp
R718KA2
ReadConfig
ReportReq
ReadConfig
ReportRsp
(1) Configure the device parameter MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v, CurrentChange= 5mA
Downlink: 0144003C003C0105000000
Device Return:
8144000000000000000000 (configuration success)
8144010000000000000000 (configuration failure)
(2) Read the device parameter
Downlink: 0244000000000000000000
Device Return:
8244003C003C0105000000 (device current parameter)

5.3 Example for MinTime/MaxTime logic

Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
S
leeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Cmd
Device
ID
Type
MinTime
0x01
(2bytes Unit:s)
0x81
0x44
0x02
MinTime
0x82
(2bytes Unit:s)
Wakes up and collects data
REPORTS 3.5V
NetvoxPayLoadData
MaxTime
BatteryChange
(2bytes Unit:s)
(1byte Unit:0.1v)
Status
(0x00_success)
(9Bytes,Fixed 0x00)
MaxTime
BatteryChange
(2bytes Unit:s)
(1byte Unit:0.1v)
MaxTime
S
leeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
7
CurrentChange
(1byte Unit:1mA)
Reserved
(8Bytes,Fixed 0x00)
Reserved
CurrentChange
(1byte Unit:1mA)
Reserved
(3Bytes,Fixed
0x00)
Reserved
(3Bytes,Fixed
0x00)