ReadConfig
ReportRsp
(1) Configure the device parameter MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v, ADCRawValue Change= 100mv
Downlink: 012A003C003C0100640000
Device Return:
812A000000000000000000 (configuration success)
812A010000000000000000 (configuration failure)
(2) Read the device parameter
Downlink: 022A000000000000000000
Device Return:
822A003C003C0100640000 (device current parameter)
5.3 Example for MinTime/MaxTime logic
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
S
leeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
MinTime
0x82
(2bytes Unit:s)
Wakes up and collects data
REPORTS 3.5V
MaxTime
BatteryChange
(2bytes Unit:s)
(1byte Unit:0.1v)
MaxTime
S
leeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
7
ADCRaw
Reserved
Value Change
(2Bytes,Fixed
(2byteUnit:1mV
0x00)