Note:
MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V
Sleeping(MinTime)
sleeping
th
0H
15
Wakes up and
Wakes up and
collects data
collects data
REPORT 3.6V
3.6V
Does not report
Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V
sleeping
sleeping
th
0H
15
M
Wakes up and
Wakes up and
collects data
collects data
REPORTS 3.6V
3.6V
Does not report
Notes:
1) The device only wakes up and performs data sampling according to MinTime Interval. When it is on sleeping mode, it does not
collect data.
2) The data collected is compared with the last data reported. If the data variation is greater than the ReportableChange value, the
device reports according to MinTime interval. If the data variation is not greater than the last data reported, the device reports
according to MaxTime interval.
3) We do not recommend to set the MinTime Interval value too low. If the MinTime Interval is too low, the device wakes up
frequently and the battery will be drained soon.
4) Whenever the device sends a report, no matter resulting from data variation, button pushed or MaxTime interval, another cycle of
MinTime/MaxTime calculation is started.
MaxTime
sleeping
th
M
30
M
Wakes up and collects
data
3.5V |3.5-3.6|=0.1
REPORTS 3.5V
...
th
th
30
M
45
M
Wakes up and
collects data
3.5V
Does not report
sleeping
th
45
M
1H
Wakes up and
Wakes up and
collects data
collects data
3.6V
REPORT 3.6V
Does not report
Users push the button,
REPORTS 3.5V.
Recalculate
MaxTime.
th
1H
1H 10
M
1H 25
Wakes up and
Wakes up and
collects data
collects data
3.5V
Does not report
Does not report
8
MaxTime
Wakes up and
collects data 3.5V
Does not report
th
th
M
1H 40
M
1H 55
3.5V
2H
th
th
M
2H 10
M
Wakes up and
Wakes up and
collects data
collects data
3.5V
REPORTS
Does not report
3.5V