Connecting intelligent Touch Manager

The iTM plus adaptor is a device that increases the number of air conditioners controlled
by the intelligent Touch Manager. It needs to be connected to an intelligent Touch Manager
to provide this capability.
2.1.1

Terminal location and schematic wiring diagram

Connect the plus ADP IF terminal of the iTM plus adaptor to the plus ADP IF terminal on
the rear face of the intelligent Touch Manager. Note that these terminals have polarity. Be
sure to connect the positive wire to the "+" terminal and the negative wire to the "–" termi-
nal.
Also, connect the intelligent Touch Manager to the termination of the wiring.
<Terminal location and schematic wiring diagram>
A
B
C
D
E
2.1.2

Wiring specifications

• Cable type: CPEV or FCPEV cable
• Core thickness: AWG22-19
• Cable length: The overall cable length between the intelligent Touch Manager and the
• Wiring connection type: sequential connections
English
intelligent Touch Manager
(For details, refer to the "intelligent Touch Manager Installation Manual (EM11A018)".)
iTM plus adaptor
plus ADP IF (intelligent Touch Manager)
plus ADP IF (iTM plus adaptor)
iTM plus adaptor on which termination resistor must be enabled
terminal iTM plus adaptor is 164 ft. or less.
Installation Manual 3P291714-4B
DCM601A72 iTM plus adaptor
13