Point Lists

2.1 Binary Input Points

2.1
Binary Input Points
Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (Binary Input with Status)
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time)
Point
Index
Overcurrent Time Protection
0
50/51 PH ACT
1
50N/51N ACT
2
50(N)/51(N) PU
3
50/51 Ph A PU
4
50/51 Ph B PU
5
50/51 Ph C PU
6
50N/51NPickedup
7
50 (N)/51(N)TRIP
Directional Overcurrent Time Protection
8
67 ACTIVE
9
67N ACTIVE
10
67/67N pickedup
11
67 A picked up
12
67 B picked up
13
67 C picked up
14
67N picked up
15
67/67N TRIP
Frequency Protection
16
81 ACTIVE
17
81-1 picked up
18
81-2 picked up
19
81-3 picked up
20
81-4 picked up
21
81-1 TRIP
22
81-2 TRIP
23
81-3 TRIP
24
81-4 TRIP
Voltage Protection
25
27 ACTIVE
26
27-1 picked up
27
27-1 TRIP
28
27-2 picked up
20
Name
50/51 O/C is ACTIVE; ON = 1, OFF = 0
50N/51N is ACTIVE; ON = 1, OFF = 0
50(N)/51(N) O/C PICKUP; ON = 1, OFF = 0
50/51 Phase A picked up; ON = 1, OFF = 0
50/51 Phase B picked up; ON = 1, OFF = 0
50/51 Phase C picked up; ON = 1, OFF = 0
50N/51N picked up; ON = 1, OFF = 0
50(N)/51(N) TRIP; ON = 1, OFF = 0
67/67-TOC is ACTIVE; ON = 1, OFF = 0
67N/67N-TOC is ACTIVE; ON = 1, OFF = 0
67/67N picked up; ON = 1, OFF = 0
67/67-TOC Phase A picked up; ON = 1, OFF = 0
67/67-TOC Phase B picked up; ON = 1, OFF = 0
67/67-TOC Phase C picked up; ON = 1, OFF = 0
67N/67N-TOC picked up; ON = 1, OFF = 0
67/67N TRIP; ON = 1, OFF = 0
81 ACTIVE; ON = 1, OFF = 0
81-1 picked up; ON = 1, OFF = 0
81-2 picked up; ON = 1, OFF = 0
81-3 picked up; ON = 1, OFF = 0
81-4 picked up; ON = 1, OFF = 0
81-1 TRIP; ON = 1, OFF = 0
81-2 TRIP; ON = 1, OFF = 0
81-3 TRIP; ON = 1, OFF = 0
81-4 TRIP; ON = 1, OFF = 0
27 under voltage protection is ACTIVE; ON = 1, OFF = 0
27-1 under voltage picked up; ON = 1, OFF = 0
27-1 under voltage TRIP; ON = 1, OFF = 0
27-2 under voltage picked up; ON = 1, OFF = 0
SIPROTEC Compact, Feeder Protection and Recloser Controller 7SC80, Bus Mapping/Point Lists
Description
C53000-L2040-C353-3, Edition 09.2018
Class
3
3
2
2
2
2
2
2
3
3
2
2
2
2
2
2
3
2
2
2
2
2
2
2
2
3
2
2
2