Pdu Requirements For Rackless Systems; Pdu Requirements, Common; Table 2-2. System Power Requirements; Table 2-3. Component Power Measurements - Quantum ActiveScale X100 Facility Requirements Manual

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Site Requirements Guide
Specification
Component Weights

2.3 PDU requirements for rackless systems

PDUs are not supplied for the rackless version of ActiveScale X100. Follow these PDU requirements to
ensure that the system will function as designed. This section provides information that is necessary in
making the determination about selecting a PDU that will effectively and safely support the power
consumption of the system. The following table lists the power specifications of the system.

Table 2-2. System Power Requirements

Parameter
Power Connector Type
Number of Connectors
Nominal System Power Required (W)
Maximum System Power Required (W)

Table 2-3. Component Power Measurements

Component
Management Interconnect
System Interconnect
System Node
Storage Node
Storage Enclosure Basic

2.3.1 PDU requirements, common

The system is configured to have two separate, AC source circuits to provide fully redundant power. Thus,
each source circuit must be able to provide the full power to the system. Typically, each source is provided
to a single socket wired into one of the customer's AC circuits. However, certain customers may have
power configurations that will not provide the required amount of power in a single connection. For
example, there could be a lower power single phase PDU where one PDU cannot provide enough power
for the ActiveScale X100 system. For these power configurations, up to two power connections will be
used for each "source" of the system.
Storage Enclosure Basic: 107kg/236lbs
Storage Node: 12.25kg/27bs
System Node: 12.25kg/27lbs
System Interconnect: 9kg/20lbs
Management Interconnect 1.9kg/4.14lbs.
Minimum Configuration
All connectors on each component are C14. The system comes with C13
to C14 cables. If these cables are not compatible with the site's selected
PDU and power equipment, the user must provide compatible cables.
35
2.90kW
4.0kW
Average Active Power
9W
83W
196W
200W
804W
15
Value
Full Configuration
35
6.50kW
7.60kW
Maximum Active Power
9W
85W
228W
229W
873W