Choosing a Location
Installation
Requirements
Rack Space
Requirements
Table 2 Rack Requirements
Environmental
Conditions
Choosing a Location
Quantum recommends installing the DXi6701/DXi6702 system in a controlled or
restricted area to prevent access by untrained personnel. In addition, Quantum
recommends that system installation be performed only by qualified IT personnel.
When choosing an installation site for the DXi6701/DXi6702 system, consider the
following requirements:
•
Installation Requirements
•
Rack Space Requirements
•
Environmental Conditions
DXi6701 and DXi6702 Site Planning Guide
Review the
site meets the installation requirements for the DXi6701/DXi6702. You can obtain
DXi6701 and DXi6702 product documentation at:
dxi6700docs
Table 2
contains the rack requirements for the DXi6701/DXi6702 components.
Height
Width (side to side)
Depth (front to
back)*
Weight (stand alone)
Air Clearance
* Without the round-hole to square-hole adapter, the depth of the node or expansion
module is 25.5 in. (64.8 cm).
The installation site must have the following environmental conditions:
• Humidity: 20% to 80% (non-condensing)
• Temperature: 50° to 95°F (10° to 35°C)
• Altitude: –100 to 10,000 ft. (–30 to 3048 m)
on page 3
on page 3
on page 3
http://www.quantum.com/
Model 6701/6702 Node
3U, 5.2 in. (13.2 cm)
17.2 in. (43.7 cm)
26.5 in. (67.3 cm)
72 lbs. (32.7 kg)
Open 4 in. (10.2 cm) behind unit for proper air flow
DXi6701/DXi6702
(PN 6-67200) to ensure that your
Expansion Module
2U, 3.5in (8.9 cm)
17.2 in. (43.7 cm)
26.5 in. (67.3 cm)
52 lbs. (23.6 kg)
3