Quantum ActiveScale X100 Facility Requirements Manual page 20

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Site Requirements Guide
Input Power Available
Input Connector and Wiring
Input Wire Connections
Input Plug Compliant To
Input Plug Color Code
Input Plug Ground Socket Position
Input Cord Wire Gauge
Output Voltage
Nominal
Operating Range
Branch Circuit Characteristics
Number of Branches
Total Available Steady State Current (per branch)
Short Term Peak (per branch)
Output Connector Ratings
C13 Steady State Current
C13 Short Term Peak Current
C19 Steady State Current
C19 Short Term Peak Current
Dimensions and weights
Width
Height
Depth
Weight
8.6kVA at 208VAC, 24Amp
3P+PE (3-Poles plus Protective Earth), 4-wire
NEMA L15-30P
N/A
N/A
10AWG or equivalent
208VAC
200VAC-220VAC
3
<=13.8A, balanced
<=20A
12A
15A
16A
20A
2.2 in. / 55 mm
70.5 in. / 1791 mm
2.2 in / 55 mm
18 lbs. / 8.2 kg
20

Advertisement

Table of Contents
loading

Table of Contents