Quantum ActiveScale X100 Facility Requirements Manual page 12

Hide thumbs Also See for ActiveScale X100:
Table of Contents

Advertisement

ActiveScale™ X100 Site Requirements Guide
Condition (fully configured)
Thermal output
Weight
1.Values are for one additional node. System Expansion Node kits can contain up to three additional nodes.
2.Rackless system height can vary based on the installation. A rackless configuration uses 36U of equipment.
3.The minimum system weight does not include the rack and PDUs
Non-operating
N/A
• Minimum system weight
• Full system weight—2227 lbs (1010 kg)
• Delivery weight (system and packaging)—2457 lbs (1114 kg)
12
Operating
Base configuration (one column of
populated sleds):
• 8.53/11.26 KBTU/h
Base +1 configuration (two column of
populated sleds):
• 10.75/13.59 KBTU/h
Base +2 configuration (three column of
populated sleds):
• 12.96/15.92 KBTU/h
Base +3 configuration (four column of
populated sleds):
• 15.17/18.25 KBTU/h
Base +4 configuration (five column of
populated sleds):
• 17.38/20.58 KBTU/h
Base +5 configuration (six column of
populated sleds):
• 19.59/22.91 KBTU/h
Full configuration (base +6, seven columns
of populated sleds):
• 21.83/ 25.25 KBTU/h
System Expansion Node kit:
• 0.665 to 0.785 KBTU/hour
3
—1572 lbs (713 kg)
1

Advertisement

Table of Contents
loading

Table of Contents