Servicing Space Requirements; Pdu Requirements; Table 2-3. Space Requirement Specifications - Quantum ActiveScale P100 Site Preparation And Requirements Manual

Table of Contents

Advertisement

ActiveScale™ P100 Site Requirements Guide
available in the location where the system will operate, consider building the system outside the
operational location and moving it into location when finished.
• If the system will be moved after being built, measure the size of the rack and check the walking path
to ensure that the rack will fit as it moves through the deployment site.
Important: Before moving the system, verify that the rack can support the
dynamic load of the system weight during movement. For details, see
requirements

2.6 Servicing space requirements

Important: Mounting a PDU or other equipment vertically in the rack can
hinder the ability to service components.
To properly install and service system components, the ActiveScale P100 system requires space at the
front and rear of the system.

Table 2-3. Space requirement specifications

Specification
Minimum front of rack space
Minimum rear of rack space
1.The length of the longest system component plus the space necessary to service system components.
2.The space required by a technician to service all of the parts at the rear of the system.
Figure 2-1. Minimum servicing space required
560mm /
22in.
REAR

2.7 PDU requirements

Use the following guidelines to ensure proper system airflow:
• The airflow in and out of the equipment must not be restricted.
• Controlled air conditioners that are functional and can sufficiently maintain specified system
operating temperatures should be located in the facility where the system will be installed.
• If rack doors will be used, ensure that the solution used with the system does not prevent airflow from
the cold aisle from entering the system freely.
on page 12.
1
2
Top of Rack
48 in (1220 mm)
22 in (560 mm)
1220mm /
48in.
FRONT
15
Rack
Value