5. POWER SUPPLY MODULE
No.
Name
[4]
LG terminal
Power supply input
[5]
terminals
Power supply input
[6]
terminals
[7]
Terminal screw
[8]
Terminal cover
[9]
Module fixing screw
Grounding for the power supply filter. The potential of A1S61P or A1S62P terminal is 1/2 of the input
voltage.
Used to connect a 24 V DC power supply.
Used to connect 100 V AC to 200 V AC power supply.
M3.5 × 7
The protective cover of the terminal block.
Used to fix the module to the base unit.
(M4 screw, tightening torque : 59 to 88 N·cm
POINT
(1)
Do not cable to the unused terminals such as FG and LG on the terminal
block (terminals whose name is not printed on the terminal cover).
(2)
Be sure to ground the terminal
with class D (class-3) grounding or above.
Description
LG to the protective ground conductor