Power Supply Via Plug Connector - Eaton XP-504-10-A10-A01-2B Manual

Table of Contents

Advertisement

3.5.2 Power supply via plug connector

CAUTION
Arrange for an electrician to install the power supply for the plug
connectors.
The required connector for the device is included as standard.
Plug connector
need for
MSTBT 2.5/3-ST-5.08 Panel-PC , Terminal and Terminal with Extender RX
MSTBT 2.5/3-ST-5.08 Box-PC with functional earth
MSTBT 2.5/4-ST-5.08 XP-504-EXT module
Connect the individual conductors.
7 mm (0.28")
solid
Use the plug to terminate the connection cable for the power supply in advance.
Plug the pre-assembled plug into the socket on the enclosure.
Pay attention to the polarity "+24V" and "0V".
Connect the power supply cable to a 24 VDC power supply that meets the requi-
rements for safety extra-low voltages (SELV) set forth in IEC/UL 61010-2-201.
Tab. 10: Specifications for connection to 24 VDC power supply
Specifications connection 24 VDC power supply
Copper conductor
Cross-section
Tightening torque
Strip length
XP-504 04/2022 MN048028EN Eaton.com
3.5 Preparing the device for operation
Use copper wire only, designed for a temperature of at least 65 °C
2
at least 0.75 mm
/ max. 2.5 mm
min. AWG19 / max. AWG14
0.5 - 0.6 Nm (4.4 -5.3 lb-in)
for the screws on the respective plug connector
7 mm
Terminal capacity
in mm²
0.75 to 2.5
AWG19-AWG14
2
(drain wire or conductor)
3. Installation
63

Advertisement

Table of Contents