1.9 Use in hazardous locations - ATEX

The II 3D Ex tc IIIC T70°C U ATEX certification applies to devices with a Widescreen
terminal:
Panel-PCs, Terminals, and Terminal with Extender RX.
EXPLOSION HAZARD
Death, serious injury, and property damage may occur if the device
is being used in a potentially explosive (classified) location and,
during operation, an electrical plug-in connection is disconnected or
the device is exposed to dangerous impacts or other types of dan-
gerous mechanical shock.
Use the device in the following environments only:
Non-hazardous (non-explosive) areas
l
Potentially explosive atmosphere, Zone 22 (according to ATEX
l
Directive), only these devices:
XP-504-..-A10-A01-2. (Panel-PC)
l
XP-504-..-TERMINAL and
l
XP-504-..-TERMINAL-EXT
l
The ground resistance of accessible metal parts must be less
than 10
Make sure that the device is not exposed to dangerous impacts
and other types of dangerous mechanical shock.
De-energize the device before disconnecting plug connections.
Clean only with a clean soft antistatic damp cloth.
When used in a potentially explosive atmosphere, Zone 22:
The XP-504...-A10-A01-..., XP-504-..-TERMINAL and XP-504-..-
TERMINAL-EXT are designed for installation in the front of
enclosures in protection type "tc" (alternatively "ta" or "tb"). This
installation must be tested and certified separately. The maxi-
mum surface temperature at the outer surface is set to 70°C at
the maximum ambient temperature of 45°C. The environment
has to be designed to avoid any bunch discharge. For safe instal-
lation, comply with the specification to holding brackets and
tightening torque in the respective Instruction leaflet for the
device.