3. Installation

3.2 Installation position

3.2 Installation position
3.2.1 Panel-PC, Terminal and Terminal with Extender RX

3.2.1.1 Mounting position

3.2.1.2 Mounting position
42
The following must be taken into account when selecting the installation position
indoors:
The size of the installation cutout depends on the device type:
l
10.1" (25.65 cm): e = 256 mm (10.07") ±0.5 (0.02"), f = 175 mm (6.88") ±0.5 (0.02")
15.6" (39.6 cm): e = 388 mm (15.28") ±0.5 (0.02"), f = 239 mm (9.40") ±0.5 (0.02")
21.5" (54.6 cm): e = 519 mm (20.43") ±0.5 (0.02"), f = 313 mm (12.32") ±0.5 (0.02")
e
Make sure that the material at the installation location is sufficiently thick
l
Material thickness of 1.5 mm (0.06") ≦ d ≦ 4 mm (0.16")
and flatness of
≦ 0.5 mm (0.02") at the installation cutout with a surface rough-
ness
Rz ≦ 120; IP 65 → DIN ISO 2768-2 (K)
The Panel-PC, Terminal, and Terminal with Extender RX devices in the XP-504 series
are designed for installation in landscape or portrait orientation.
Fig. 8: Mounting position
It can be mounted in a perfectly vertical position or at an angle of up to max. - 45° ≦ α
≦ max. + 10° in the directions shown below.
If the device is not mounted in a perfectly vertical position, make sure that air will still
be able to circulate properly through the openings in the housing.
XP-504 04/2022 MN048028EN Eaton.com