iSitePower-M V100R002C00 (MAP15A1, MAB05B1)
User Manual
A.1 Environmental Specifications
Table A-1 Environmental specifications
Item
Operating temperature
Transportation temperature
Storage temperature
Relative humidity
Altitude
Noise level
IP rating
Operating environment
Other requirements
Issue 01 (2021-09-30)
A
Technical Specifications
Specifications
0–45°C
–40°C to +70°C
–40°C to +70°C
5%–95% RH
0–4000 m. (When the altitude ranges from 2000 m to 4000
m, high temperature derating applies and the operating
temperature decreases by 1°C for each additional 200 m.)
≤ 40 dBA at 1 m at 30°C ambient temperature
IP65
Class C environment
● There should be no conductive dust, corrosive gas, or
explosion hazard.
● Dust, corrosive substances, pests, molds, and other
indicators should be controlled in accordance with Class
4.1 requirements in ETSI EN 300 019-1-4 (V2.2.1).
Copyright © Huawei Digital Power Technologies Co., Ltd.