    15. Ordering example ......................23 © 09.2021 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab’s products, systems, product and product group designations are protected by intellectual property rights (IPR).
  • Page 3: General Information

    • Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3. Temperature in the place of installation is permitted to range from -20°C to +50°C. Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03...
  • Page 4: Design

    The cable entry must meet a minimum fire resistance of 30 minutes. Fig.1 Damper SDJR-S - actuating mechanism in the cover Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 5 Cable 1m, 6x0,75mm Cable 1m, 6x0,75mm Cable 1m, 6x0,75mm (BEN 24-ST) with plug connectors Fig. 2 Actuator BELIMO BEN 24(-ST) Fig. 3 Actuator BELIMO BEN 24-SR Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 6 Cable 1m, 3x0,75mm - auxiliary switch Cable 1m, 6x0,75mm Cable 1m, 6x0,75mm Cable 1m, 6x0,75mm (BEE 24-ST) with plug connectors Fig. 5 Actuator BELIMO BEE 24(-ST) Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 7 | we s i mp l if y con s t r uct i on Smoke Control Damper SDJR-S Fig. 6 Actuator BELIMO BEE 24-SR Fig. 7 Actuator BELIMO BEE 230 Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 8 Cable 1m, 3x0,75mm - auxiliary switch Cable 1m, 6x0,75mm (BE 24-ST) with plug connectors Fig. 8 Actuator BELIMO BE 24-12(-ST) Fig. 9 Actuator BELIMO BE 230-12 Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 9 The cable entry must meet a minimum fire resistance of 30 minutes. For more information on actuators and devices, see the Belimo catalogue. Fig. 10 Damper SDJR-S - actuating machanism and BKNE in the cover Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03...
  • Page 10 + green dark network outage Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 11 III (low voltage) Degree of protection IP 20 Ambient operation temperature 0 …+50°C Connection screw terminals for 2x1.5mm conductor Fig. 12 Communication and control devices BKSE 24-6 Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 12: Dimensions, Weights

    1. Damper body BEN / BEE 176,5 2. Damper plate 186,5 3. Actuating mechanism cover BEN / BEE + 236,5 BKNE BE + BKNE 251,5 Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 13 0.3075 x1000 40.6 0.2210 x1000 47.0 0.3485 x1100 43.9 0.2410 x1100 50.9 0.3801 x1200 46.1 0.2670 x1200 53.4 0.4211 * table continues on next page Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 14 0.7200 x1000 57.5 0.5610 x1000 70.2 0.8160 x1100 x1100 62.5 0.6118 76.5 0.8899 x1200 65.6 0.6778 x1200 80.2 0.9859 * table continues on next page Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 15 90.0 1.1913 Example, how to calculate effective area and size of SDJR-S damper [AxB], when knowing air volume in [m³/s] or [m³/h] on damper. Maximum allowed air velocity on SDJR-S is 12 [m/s]. Formula: Sef = Q / v Q …...
  • Page 16: Placement And Assembly

    5. Washer C 6. Wall construction without fire resistance 7. Atypical protection box with access to actuator from side, not as standard from the top Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 17: Suspension System

    6. Hinge plate - min. thickness 10 mm 7. Concrete screw tested for fire resistance R30-R90, max. Tension up to 0.75 KN (length 35 mm) Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 18: Technical Data

    | we s im pli f y co ns tr u c t io n Smoke Control Damper SDJR-S Technical data 6. Pressure loss Diagram 6.1. Pressure drops of the damper was determined for air density 1,2 kg/m Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 19: Noise Data

    - frequency of octave band Tab. 7.1.2. Sound power level Lw in dB(A) for B=350/500/700/900/1100mm, damper fully open f (Hz) 1000 2000 4000 8000 Total Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 20: Material, Finish

    Inspection, testing 9. Inspection, testing 9.1. 9.1. The appliance is constructed and preset by the manufacturer, its operation is dependent on proper installation and adjustment. Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 21: Transportation And Storage

    To connect the actuator, use the prepared hole in the box, which is equipped with PROMASEAL foaming tape. If necessary, the hole can be additionally filled with fire-resistant sealant. Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03...
  • Page 22: Entry Into Service And Revisions

    13.1. Spare parts are supplied only on basis of an order. Product data 14. Product label 14.1. Product label is placed on the damper casing Fig. 17 Product label (Nameplate) Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 23: Ordering Information

    | we s i mp l if y con s t r uct i on Smoke Control Damper SDJR-S Ordering information 15. Ordering example SDJR-S 230V Yes 30mm Product Width Height Actuator Insulated blade Flanges/grilles Example: SDJR-S-200-200-230V-Insulated-30mm Lindab reserves the right to make changes without prior notice Last modified: 2021-09-03 Rev: 2021-03-26...
  • Page 24 At Lindab, good thinking is a philosophy that gui- des us in everything we do. We have made it our mission to create a healthy indoor climate – and to simplify the construction of sustainable buil- dings. We do that by designing innovative pro- ducts and solutions that are easy to use, as well as offering efficient availability and logistics.