Z O N E :
B 0 1 : P 0 0 1 - 0 0 2
3.2.3.3.4.- Configure element sensitivity...............................................................................Menu_9
From this menu we can vary the sensitivity of the points individually (indicating the loop and point
number). There are three levels of sensitivity: HIGH, MEDIUM AND LOW (all the sensors come with
average sensitivity).
3.2.3.3.5.- Additional passwords..........................................................................................Menu_20
From this menu we can introduce an additional password for the access level 2 and another one for the
access level 3, except the numbers 00 and 0000. Whenever we introduce a new password it deletes the
one that had been previously entered. The standard Passwords that the control panel have are: access
level 2: 27; and access level 3: 9000).
3.2.3.3.6.- Configure auto-evacuation...................................................................................Menu_9
Within this menu we have four submenus: ENABLE AUTOEV., DISABLE AUTOEV., CONFIGURE
DELAY and AUTO EVACUATION SUMMARY. Automatic evacuation is a function that activates
the relays configured as sounder and/or switches if there is an alarm in the system and the alarm has not
been reset during the configured delay.
ENABLE AUTOEV.: Automatic evacuation is activated by this option.
DISABLE AUTOEV.: Automatic evacuation is deactivated by this option.
CONFIGURE DELAY: The delay period that occurs between the alarm being raised and the
siren and/or switch relays being activated is configured with this option. The maximum delay is
9 minutes and 59 seconds.
AUTO EVACUATION SUMMARY: In this option we will be able to see the status of
automatic evacuation and its delay.
Digital fire detection control panel
Label
B 1
D E T
1 Y 2 .
B 0 1 : P 0 0 6 - 0 0 6
Zone List
Zone List
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
COMPACT LYON PLUS
cofem@cofem.com
www.cofem.com
Zone number
Z O N E :
0 0 1