system. Furthermore, the sub-lists are related to each other by the logical command
AND (&) and OR (/). The AND (&) command means that the trigger conditions of
that sub-list must be given with that of the next one. The OR (/) command means
that the trigger conditions of that sub-list must be given "or" that of the next one.
Below are some examples.
Case 1:
R E L A Y :
1
C T R L : 0 1
2
C T R L : 0 0
3
C T R L : 0 0
List (sub-list)
In this case, relay 01 will be activated when there are more than 3 sensors in alarm state from 9 sensors that
are present in the LOOP_01 in Control_Panel_01
Case 2:
R E L A Y :
1
C T R L : 0 1
2
C T R L : 0 0
3
C T R L : 0 0
In this case the RELAY_01 will be activated by Control_Panel_01 from LOOP_01 when sensor 1, 5 and 9 are
all of them in alarm state, and our relay may be in that loop or another.
Very important to notice is the logic operator "OR" that should ALWAYS be at the end of any list (sub-
list), otherwise the relay 01 will never be activated.
Case 3:
R E L A Y :
1
C T R L : 0 1
2
C T R L : 0 2
3
C T R L : 0 3
In this last scenario, the "RELAY 1" will be activated only when all 3sensors defined in different
Control_Panels in network are in alarm state.
VIEW CONFIGURATION: View the configuration of the relay and all its
parameters.
R E L A Y :
M D A 2 Y
D A Y
N I G H T
VIEW DELAY LISTS: View the list of points configured for the relay.
Digital fire detection control panel
COMPACT LYON PLUS
Relay Number
Loop number
1
L A B E L :
L O O P : 0 1
L O O P : 0 0
L O O P : 0 0
Control_Panel
1
L A B E L :
L O O P : 0 1
L O O P : 0 0
L O O P : 0 0
1
L A B E L :
L O O P : 0 1
L O O P : 0 1
L O O P : 0 1
R e l a y
M a n e u v e r
M a n e u v e r
D e t e c t o r : Y e s
D e t e c t o r : Y e s
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
cofem@cofem.com
First point
A L R M : 3
P N T S : 0 0 1 : 0 0 9
A L R M : 0
P N T S : 0 0 0 : 0 0 0
A L R M : 0
P N T S : 0 0 0 : 0 0 0
Alarms
A L R M : 1
P N T S : 0 0 1 : 0 0 1
A L R M : 1
P N T S : 0 0 5 : 0 0 5
A L R M : 0
P N T S : 0 0 9 : 0 0 9
A L R M : 1
P N T S : 0 0 1 : 0 0 1
A L R M : 1
P N T S : 0 0 5 : 0 0 5
A L R M : 1
P N T S : 0 0 9 : 0 0 9
R e l a y
L o o p :
0 0 2
C a l l : Y e s
C a l l : Y e s
–
www.cofem.com
Last point
/
/
/
Logic (OR, AND)
&
&
/
&
&
/
0 0 2
P o i n t : 0 0 3
D e l a y :
0 0