1.5.6.2- Operation and configuration

Each control panel in the network displays all information from other control panel and interact with
each other.
Once the Control Panel is up, proceed to assign a different number to each Control Panel.
For this we perform the following:
Menu (code 27)  4- System Setup (code 9000)  8- Communications  4- Set control panel
number.
After the configuration should perform a general reset at each control panel of the network. For this we
perform the following sequence: Menu (code 27)  8- General reset.
A control panel in the network can perform the same functions as any normal control panel. You can
also perform the following functions on the rest of the control panels of the network:
Reset alarms and faults in the network control panels.
Reset all the network control panels.
Enable or disable without delay mode in all network control panels.
Enable or disable sirens stop in all network control panels.
Enable or disable the evacuation in all network control panels.
Enable or disable manual mode in all network control panels.
Disable the buzzer in all network control panels.
Digital fire detection control panel
COMPACT LYON PLUS
Menu_Control_Panel
FIRE PROTECTION MANUFACTURER
C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 –
cofem@cofem.com
www.cofem.com
43

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the COMPACT LYON PLUS and is the answer not in the manual?

Table of Contents