Digital fire detection control panel LYON REMOTE PLUS Index 1.- System description .................................6 1.1.- Introduction ..............................6 1.2.- Principle of operation ............................6 1.3.- Characteristics ..............................7 1.4.- Composition of the control panel ........................7 1.5. – Loop Elements Capacity ...........................
Page 3
Digital fire detection control panel LYON REMOTE PLUS 2.2.3.- Power supply auxiliary outputs and charging of power source batteries..............48 ..............................49 2.3.- Components. 2.3.1.- Batteries.................................49 2.3.2.- Connection schematic of a typical loop........................49 2.3.3.- Sounder and controls with relays...........................51 2.3.3.1.- Connection of the internal two tone 24V Sounder (SIR-24B/SIR-24BL) ............51...
Page 4
Digital fire detection control panel LYON REMOTE PLUS 3.2.3.3.9- Send Zones to Repeaters.........................77 3.2.3.4.- Update date and time............................77 3.2.3.5.- Day/ Night timetable............................77 3.2.3.6.- Put into test/ normal mode..........................77 3.2.3.7- Led ON / OFF…………….............................77 3.2.3.8.- Language menu. ……………..........................77 3.2.3.9.- Communications.
Page 5
Digital fire detection control panel LYON REMOTE PLUS CERTIFICATION 0099 C/ Compositor Wagner,8 —P.I. Can Jardí CP 08191-- Rubí, Barcelona (España) 09 / 10 0099/CPR/A74/0074 – 0099/CPR/A74/0100 EN 54-2 EN 54-4 Equipo de control e indicación para sistemas de detección y Equipo de suministro de alimentación de sistemas de...
With this type of system, not only we can vary the sensitivity of the sensor, but we can even adapt the sensitivity to the environmental conditions. Each sensor on the Cofem Addressable Detection System transmits its analogue value to the control panel with a regularity of less than 10 seconds. The control panel gathers the readings from each sensor and determines the status thereof according to these instant readings, any previous readings (history), the pre- programmed parameters and on the decision algorithm.
Digital fire detection control panel LYON REMOTE PLUS 1.3.- Characteristics Base control panel configurable and expandable from 1 to 20 loops. Allows 226 connection elements per loop. All the loop elements are monitored, except the KABY loop isolator.
Digital fire detection control panel LYON REMOTE PLUS In a single box we will be able to connect 2 loop controllers and their 4 corresponding loop drivers. Therefore for configurations in excess of 8 loops we will need two boxes.
Page 9
Digital fire detection control panel LYON REMOTE PLUS FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
Page 10
Digital fire detection control panel LYON REMOTE PLUS FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
Digital fire detection control panel LYON REMOTE PLUS 1.5.1.- Addressable sensors ( A30 series) 1.5.1.1.- Addressable smoke sensors (A30XHA & A30XHA-S) The addressable smoke sensors measure the smoke particle concentration by unit of volume present in the atmosphere. If we designate by Y an un-...
Digital fire detection control panel LYON REMOTE PLUS 1.5.1.2.- Addressable temperature sensor (A30XTA) The Addressable Temperature Sensor (A30XTA) measures the room temperature, as well as its rate of change. When the ambient temperature experiences slow rates of change (less than 1ºC / min), the Alarm level remains constant to 60ºC.
Digital fire detection control panel LYON REMOTE PLUS 1.5.1.3.- Addressable multi-sensor (A30XHTCO) The addressable multi-sensor A30XHTCO has three detection types: monoxide, temperature and smoke. The addressable multi-sensors is able to measure three types of parameters so the control panel compute the average by means of a dynamic processing algorithm which will vary with the three phenomena.
Page 14
Digital fire detection control panel LYON REMOTE PLUS Figure 2A. Wiring Diagram of A30XHA, A30XTA, A30XHTCO and PUCAY devices FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 –...
Digital fire detection control panel LYON REMOTE PLUS 1.5.2- Addressable sensors ( A50 series ) 1.5.2.1- Addresable Smoke-Heat and CO sensors with Isolator (A50SHCOI) The A50 family of detectors are based on a new refined aesthetic that integrates the latest electronic technology with new, more efficient detection algorithms and a three-dimensional design that makes it more robust against environmental dirt.
Digital fire detection control panel LYON REMOTE PLUS 1.5.2.2 Smoke-Heat addressable sensors with/without isolator (A50SHI / A50SH) The A50 family of detectors are based on a new refined aesthetic that integrates the latest electronic technology with new, more efficient detection algorithms and a three-dimensional design that makes it more robust against environmental dirt.
Digital fire detection control panel LYON REMOTE PLUS 1.5.2.3- Smoke addressable sensors with/without isolator (A50SI / A50S) The A50 family of detectors are based on a new refined aesthetic that integrates the latest electronic technology with new, more efficient detection algorithms and a three-dimensional design that makes it more robust against environmental dirt.
Digital fire detection control panel LYON REMOTE PLUS 1.5.2.4- Heat addressable sensors with/without isolator (A50HI / A50H) The A50 range of detectors is based on a new refined aesthetic that integrates the latest electronic technology with new, more efficient detection algorithms and a three-dimensional design that makes it more robust against environmental dirt.
Page 19
Digital fire detection control panel LYON REMOTE PLUS Figure 2B. Schematic diagram for the A50 family and PUCAY NOTE: If the detector has ISOLATOR the POLARITY must be RESPECTED (B negative, A1 loop input positive B2 loop output positive.) FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I.
Digital fire detection control panel LYON REMOTE PLUS 1.5.3.- Addressable alarm Manual Call Point (PUCAY) Microprocessed addressable device (with short-circuit isolator) installed as one more element in the loop. The re-settable addressable manual call point (with short- circuit isolator) incorporates an action indicator (LED) which is illuminated in the case of being manually activated (alarm).
Digital fire detection control panel LYON REMOTE PLUS 1.5.4. - Modules 1.5.4.1- Master detection module (KMAY) Microprocessed addressable device (with short-circuit isolator) installed as one more element in the loop. This is a device that allows connecting conventional detectors and/or manual call point inside an addressable fire detection system acting as a bridge between the addressable detection system and the conventional one.
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.2- Technical signals module (MSTAY) Microprocessed addressable devices (with short-circuit isolator) installed as one more element in the loop. It has two inputs to distinguish between the open or close state of a dry contact connected in series with a 10 K...
Digital fire detection control panel LYON REMOTE PLUS Master relay and technical signals module (MYOA) 1.5.4.3- Microprocessed addressable devices (with short-circuit isolator) installed as one more element in the loop. This module has one relay output fed by external 30 V and one technical signal input to distinguish the open or closed state of a dry contact.
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.4- Master relays module (MDA1Y) Microprocessed addressable device (with short-circuit isolator) installed as one more element in the loop. The module take the power supply from the loop, but they require an auxiliary 30V supply to give the necessary energy to the devices controlled by the relays.
Page 25
Digital fire detection control panel LYON REMOTE PLUS Figure 6. Wiring diagram MDA1Y Figure 7. Wiring diagram MDA2Y FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 –...
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.6 –Two relay dry contact output module (MDA2YLT) Microprocessed and algorithmic-addressable module (with short-circuit insulator) which is installed as one more element in the loop. The modules are powered by the loop connection, requiring no outside power.
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.7-Module to connect 32 detectors / 10 manual call points (KMAY32) Microprocessed addressable module (with short-circuit insulator) which is installed as one more element in the loop. This module allows the connection of conventional...
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.8 –Module with 8 inputs ( MSTAY8 ) Microprocessed addressable module (with short-circuit insulator) which is installed as one more element in the loop. It has eight inputs for external equipment monitoring.
Page 29
Digital fire detection control panel LYON REMOTE PLUS Figure 10. MSATY8 wiring diagram configurations FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.9- Loop isolator (KABY) The kaby element installed as another element inside the loop (It is not addressable - There is not need to configure this element). This is a protection element that is connected into the detection...
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.10- Addressable sounder (SIRAY / SIRAYL / SIRAY+BSLC) Microprocessed addressable sounder (with short-circuit isolator) installed as another element inside the loop. This sounder is manufactured in red plastic ABS. It is a module with a single programming function respecting the timing and combination of elements that activate it.
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.11- Remote indicator (PIAL) Remote action indicator of fire detection systems. Typical cases of use: • Places where elements of the detection system are not visible, for example, inside false ceiling, in which the PIAL can be visibly situated on the lower part of the ceiling or near the wall.
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.12-Base with siren and visual alarm (A50ZSLDR / A50ZSDDR) Base for addressable sensors A30X with certified base for visual alarm and sound EN 54-23 and sound EN 54-3 powered directly from the loop.
Page 34
Digital fire detection control panel LYON REMOTE PLUS Figure 14A. Wiring diagram A50XZSDDR/A50XZSLDR Figure 14B. Configuration DIP A50XZSDDR Figure 14C. Configuration DIP A50XZSLDR FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 –...
Digital fire detection control panel LYON REMOTE PLUS 1.5.4.13-Base with siren and visual alarm (A30XZSLDR / A30XZSDDR) Base for addressable sensors A30X with certified base for visual alarm and sound EN 54-23 and sound EN 54-3 powered directly from the loop.
Page 36
Digital fire detection control panel LYON REMOTE PLUS Figure 14A. Wiring diagram A30XZSDDR/A30XZSLDR Figure 14B. Configuration DIP A30XZSDDR Figure 14C. Configuration DIP A30XZSLDR FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 –...
Digital fire detection control panel LYON REMOTE PLUS 1.5.5.- Repeaters 1.5.5.1.- Installation The repeater must be fixed on a vertical wall face. The side slots must be left free for heat to escape. The dimensions and the pre-drilled holes for cable entry are shown in the following diagram.
Digital fire detection control panel LYON REMOTE PLUS 1.5.5.2. Operation and Configuration..................Menu_25 The repeaters display all the information about alarms, disconnections, relay actuations and faults. Once the repeaters have been connected, they must then be configured in the control panel by entering the number of each repeater to be configured.
Page 39
Digital fire detection control panel LYON REMOTE PLUS The zone names must then be sent according to this sequence in the control panel: Menu (access code 27) 4. System Setup (access code 9000) 2 Configure 9 Send Zones to Repeaters.
Digital fire detection control panel LYON REMOTE PLUS 1.5.5.3.- Repeater menus The following menus are accessible in the repeater: Repeater_menu 1. SYSTEM SETUP 1.1. ADDITIONAL PASSWORDS: From this menu, an additional password can be entered for access level 2 and another password for access level 3. Every time a new password is entered, the password entered previously will be deleted.
Page 41
Digital fire detection control panel LYON REMOTE PLUS Figure 16. Repeater connection. Max 15 FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
The dimensions and pre-drilling for the cable input are in the following figure. Figure 17. Lyon box Cofem Digital Detection System allows to connect up to 15 control panels in a network, by connecting 2 wires of 1,5 mm (RS485 communication line).
Digital fire detection control panel LYON REMOTE PLUS 1.5.6.2.- Operation and configuration Each control panel in the network displays all information from other control panel and interact with each other. Once the Control Panel is up, proceed to assign a different number to each Control Panel.
Digital fire detection control panel LYON REMOTE PLUS 1.5.6.3.- Control panels network menu…………………………………………………………Menu_25 In the control panels we can find the next specific control panels network menus: VIEW CONTROL PANELS: Visualize the set control panels. RESET CONTROL PANEL NETWORK: Reset all the control panels in the network.
Digital fire detection control panel LYON REMOTE PLUS 1.6.- Accessories. 1.6.1.- PC based configuration software. Software is available for the addressable control panel LYON (I-Link), that means of which the user can perform all the control panel programming in a simple and intuitive way. With this system it will be possible to maintain the configuration for future use.
Digital fire detection control panel LYON REMOTE PLUS 2.2.- Wiring Lyon addressable system Connection of the Lyon addressable system will be carried out with 2 x 0.7 mm up to 2 x 2.5 mm BRAIDED CABLE SCREENED HALOGEN FREE, both the loops as well as the sounders, KMAY connected elements, fault outputs and 30 volt auxiliary supplies.
Digital fire detection control panel LYON REMOTE PLUS 2.2.2.- Loop driver The standard control panel can have a maximum of 4 loop drivers of 2 loops, located in its interior. In the event of needing more than 8 loops, that is to say, more than 4 drivers, the control panel will be provided with two joined boxes providing a maximum of 20 loops.
Page 48
Digital fire detection control panel LYON REMOTE PLUS 2.2.3.- Power supply auxiliary outputs and charging of power source batteries. -Battery charger and auxiliary power supply outputs Power supply board: 30v DC output Power supply supply for battery charger control...
Page 49
Digital fire detection control panel LYON REMOTE PLUS 2.3.- Components. 2.3.1.- Batteries. The supervised battery input/output allows the connection of batteries to the control panel. The batteries are charged and monitorized through this connection . The battery charge is compensated depending on the temperature of the batteries. This input/output is protected by a fuse and also against inversion of polarity.
Page 50
Digital fire detection control panel LYON REMOTE PLUS Figure 24. General Wiring Diagram FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
Page 51
Digital fire detection control panel LYON REMOTE PLUS 2.3.3.- Sounder and controls with relays. 2.3.3.1.- Connection of the internal two tone 24V Sounder (SIR-24B/SIR-24BL) Elements needed for its correct installation: 1 Resistance 33 KΩ, in the event of being connected to the general sounder the resistance is 4K7, included in the control panel and/or modules.
Page 52
Digital fire detection control panel LYON REMOTE PLUS 2.3.3.3.- Connection of the flashing internal 24V Sounder (SIR24F) Elements needed for its correct installation: 1 Resistance of 33 KΩ; in the event of the sounder being connected to the general sounder, the resistance should be 4K7, which is included in the control panel and/or the modules.
Page 53
Digital fire detection control panel LYON REMOTE PLUS 2.4- Accessories. 2.4.1.- Computer. The LYON addressable control panel system can use software (I-Link), with which the user can completely programme the control panel, easily and intuitively. By using this system, the configuration can be saved for future use.
Page 54
Digital fire detection control panel LYON REMOTE PLUS FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA. Tlf.: +34 935 862 690 – cofem@cofem.com – www.cofem.com...
Page 55
Digital fire detection control panel LYON REMOTE PLUS 3.- Operation and configuration. 3.1.- Description of the front panel. 3.1.1.- Keypad. Disable the configured relay delays Disable all relays that are configured as sirens. Activate all relays programmed as sirens and switches.
Page 56
Digital fire detection control panel LYON REMOTE PLUS Amber LED indicating a fault. The display details the type of supply fault. Amber LED indicating a supply fault. The display details the type of supply fault. Amber LED indicating the system has ceased to function correctly.
Page 57
Digital fire detection control panel LYON REMOTE PLUS Control panel menu: >LYON │ ├───1. Monitoring ├───2. Logic relay activation │ ├───2.1. List triggered Relays │ ├───2.2. Turn on one Relay │ ├───2.3. Turn off one Relay │ ├───2.4. Activate all sounders │...
Page 58
Digital fire detection control panel LYON REMOTE PLUS │ │ ├───4.2.3. Configure alarm zones │ │ │ ├───4.2.3.1. Configure zone │ │ │ ├───4.2.3.2. List to Modify │ │ │ ├───4.2.3.3. Delete zone │ │ │ ├───4.2.3.4. Labelling │ │...
Page 59
Digital fire detection control panel LYON REMOTE PLUS │ │ │ ├───4.8.3.6. Phone 3 number programming │ │ │ ├───4.8.3.7. Phone 4 number programming │ │ │ ├───4.8.3.8. Phone 5 number programming │ │ │ └───4.8.3.9. Situation Message Programming │...
Page 60
Digital fire detection control panel LYON REMOTE PLUS *Note: Only for C-Lyon and Zafir. The Lyon version only Modbus/FAC as 4.8.4 3.2.1.- Level 1 access. 3.2.1.1.- Activation of the control panel. If the control panel is starting up correctly we see:...
Page 61
Digital fire detection control panel LYON REMOTE PLUS 2. In the control panel does not find a previously configured loop controller the following message appears offering the possibility of deleting it from the controller configuration. n o t f o u n d...
Page 62
Digital fire detection control panel LYON REMOTE PLUS 3.2.1.2. Incident and anomaly display. Incidents and anomalies appear on the screen following this order of priority: Alarms Relays on Faults Disabled zones and points Test Mode Events ...
Page 63
Digital fire detection control panel LYON REMOTE PLUS Selected activation Nº alarms Disabled zones and/or points In the case of disabling a elements or zone, the control panel will illuminate the orange DISABLED LED, sound the buzzer and show the following message:...
Page 64
Digital fire detection control panel LYON REMOTE PLUS Relay number If the right cursor is pressed we will be able to see the rest of the fault information. F A U L T S P t : 0 1 > Z :...
Page 65
Digital fire detection control panel LYON REMOTE PLUS In order to change the type of incident on the screen we must press the ENTER key. 3.2.1.4. - Look up incidents. After viewing the incident that we wanted to look up, we press the right cursor to obtain in each case the corresponding screen with the rest of the incident information.
Page 66
Digital fire detection control panel LYON REMOTE PLUS 3.2.2.4.- Monitor......................Menu_1(Main) It enables the readings and the configuration of the various addressable sensors to be seen. By entering the loop and elements numbers, we can see the type (optical, thermal, relays module, master module, etc), the label and the manufacturer’s programming number.
Page 67
Digital fire detection control panel LYON REMOTE PLUS between 0 and 9 minutes 59 seconds, and disabling or enabling the relay. 3.2.2.7.- System Setup........................Menu_4 ption 4 of the main menu, SYSTEM SETUP. From this option after entering the password for level 3 access we are able to access the configuration menu.
Page 68
Digital fire detection control panel LYON REMOTE PLUS 3.2.2.10.- Welcome message......................Option_7 Option 7 of the main menu. From this option it is possible to change the welcome message. The welcome message is the text that appears on the first line when the control panel is in standby.
Page 69
Digital fire detection control panel LYON REMOTE PLUS Type of event Alarm type N U M : 0 0 3 A L A R M C A L L P O I N T L O O P : P O I N T : 0 0 5 N .
Page 70
Digital fire detection control panel LYON REMOTE PLUS 3.2.3.2.- Label points. ption 1 of the SYSTEM CONFIGURATION menu. We will have to introduce the loop and element number to label. This is an option that allows us to label each element of the system, that is to say, to give each point a description that gives us the information necessary to physically locate it in the installation.
Page 71
Digital fire detection control panel LYON REMOTE PLUS VIEW LOOP INFORMATION: In this submenu we can see the number of elements that are in the loop classified by type. A 3 0 X H A ∕ S : 0 0 4...
Page 72
Digital fire detection control panel LYON REMOTE PLUS 3.2.3.3.2.1- Configure logical relays.....................Menu18 Option 2 of the CONFIGURE menu. In this menu we have the option of configuring all the parameters referred to logical relays connected to the loop, that is to say, the type of actuation, delay, etc.
Page 73
Digital fire detection control panel LYON REMOTE PLUS of a relay to different points located in different loops and centers within the system. Furthermore, the sub-lists are related to each other by the logical command AND (&) and OR (/). The AND (&) command means that the trigger conditions of that sub-list must be given with that of the next one.
Page 74
Digital fire detection control panel LYON REMOTE PLUS 3.2.3.3.2.2.- Relay Auto. Configuration..................Menu_18 Option that allows us to configure all relay automatically (all types like SIRAY, MDA1Y, MDA2Y and MYOA/F ) except SIRDR, like immediate ALARM. This option overrides the previous relay configurations.
Page 75
Digital fire detection control panel LYON REMOTE PLUS Label Zone number Z O N E : D E T 1 Y 2 . Z O N E : 0 0 1 B 0 1 : P 0 0 1 - 0 0 2...
Page 76
Digital fire detection control panel LYON REMOTE PLUS 3.2.3.3.7- Added Delay Setup....................Menu_9 This option is activated when it is introduced a time between 1" to 9 min 59". When the first signal alarm is received, control panel actives corresponding programmed delays.
Page 77
Digital fire detection control panel LYON REMOTE PLUS day for the control panel 3.2.3.6.- Put into test/ normal mode...................Menu_12 Test mode is the operating mode that allows us to activate the alarm of any control panel element without any of the configured relays activating.
Page 78
Digital fire detection control panel LYON REMOTE PLUS changed, the labels do not change. 3.2.3.9.- Communications. ……………..................Menu_15 Option 8 of the SYSTEM CONFIGURATION menu. Within this menu we have following submenus: REPEATER NETWORK: VIEW CONFIGURED REPEATERS: display the configured repeaters on the control panel.
Page 79
Digital fire detection control panel LYON REMOTE PLUS CONTACTID TEST INTERVAL : Checking time of the communication with the receiving center. SITUATION MESSAGE PROGRAMING Message sent to the phones configured in the previous options SET CONTROL PANEL NUMBER: ...
Page 80
Digital fire detection control panel LYON REMOTE PLUS REMOTE CONECTION: It allows configuring the following communication parameters of the REMOTE card in the ethernet network. Activate/Deactivate the communications with REMOTE CARD. IP: Defines the IP address of the REMOTE card in the internal network. By default 192.168.0.254.
Page 81
Digital fire detection control panel LYON REMOTE PLUS 4.- Start-up. 4.1.- Prior verifications. Prior to putting the Lyon system installation into operation, we must assure ourselves that the installation is totally completed and we have all the data for its correct programming. For this it is necessary to verify that the points shown below have been completed: ...
Page 82
Digital fire detection control panel LYON REMOTE PLUS 4.2.- Supply NETWORK: The power to the input terminals will be 110~230V +/- 10% - 50-60 Hz Attention! Connect the EARTH cable, ensuring the right position of the neutral and phase line BATTERIES: Connect the two elements in series (Watch out for the polarity).
Page 83
Digital fire detection control panel LYON REMOTE PLUS During the startup process, the control panel may display various types of faults. For the Lyon control panel to work correctly, these faults must be resolved. For this, consult section 4.4 which describes the main faults, the causes of them and the action to be taken to resolve them.
Page 84
Digital fire detection control panel LYON REMOTE PLUS MAINS VOLTAGE DROPS (110~230V voltage does not reach the power source) 110~230V voltage does not reach the power source. Cause Check that there is 110~230V mains voltage in the terminal strip for connecting the A.C.
Page 85
Digital fire detection control panel LYON REMOTE PLUS RELAY SHORT-CIRCUITED:01 (Short circuit for the S1 General Sounder relay) There is a short circuit between the output of the S1 General Sounder relay and the end- Cause of-line resistance. Check that S1 General Sounder output is correctly connected to the sounders connected to it, check that the end-of-line resistance (4K7) and check the supervision diodes are correctly mounted (see chapters 2.3.3.1 and 2.3.3.2).
Page 86
Digital fire detection control panel LYON REMOTE PLUS CONTROLLER FOR LOOP: OX IS NOT COMMUNICATING The controller for the indicated loop has stopped working. Cause Reset the control panel. If, during start-up, the following message is shown: “CONTROLLER NOT FOUND WITH ADDRESS: 001 … 002 003 004 005”, stop the...
Page 87
Digital fire detection control panel LYON REMOTE PLUS RELAY SHORT CIRCUIT 02 (Short circuit for the relay 2 of the MDA2Y) There is a short circuit between the output of the relay 2 of the MDA2Y and the end-of- Cause line resistance.
Page 88
Digital fire detection control panel LYON REMOTE PLUS DIRTY SENSOR The permitted level of dirt has been exceeded on the sensor (A30XHA, A30XHA-S Cause ,A30XHTCO, A50S/I, A50SH/I, A50HSCOI), 100% in the monitoring screen, the sensor must be cleaned. Clean the sensor using compressed air, reset the fault and monitor the element, checking that the readings are below 5.
Page 89
Digital fire detection control panel LYON REMOTE PLUS Annex 1: Use of the Control Panel LYON / C-LYON / ZAFIR system 1. What is a control panel LYON / C_LYON /ZAFIR SYSTEM? The LYON / C_LYON / ZAFIR system is a FIRE detection system that combined with sensors and corresponding modules, is capable of quickly detecting the early signs of a fire, issuing a warning of the event and acting on various elements, such as emergency exit doors, acoustic fire alarms or crossed outputs.
Page 90
Digital fire detection control panel LYON REMOTE PLUS If the incident in question is an ALARM, the user must verify whether it is real. If so, the order to evacuate can be given. Beforehand, the keypad must be enabled and also if any of the keys on the control panel are pressed, except for the buzzer (the control panel requests a code to be entered): To enable the keypad, the access code must be entered by using the (▲▼◄►) keys:...
Page 91
Digital fire detection control panel LYON REMOTE PLUS Annex 2: Elements configuration Lyon / C-Lyon / Zafir 1. Introduction The steps necessary to configure the Addressable Control Panel LYON are given below. The addressable system includes the following elements: Addressable sensors...
Page 92
Digital fire detection control panel LYON REMOTE PLUS 2.-Keypad access If the keypad has not been enabled, the only key that will work is the stop BUZZER button (in the event of any new incidents, the buzzer will be activated again). The LYON / C-LYON / ZAFIR system provides several different access levels to the various internal functions.
Page 93
Digital fire detection control panel LYON REMOTE PLUS 3.-Configuration of points in a loop Pressing the menu button will show the main menu on the display. KEYS FOR NAVIGATING TECLAS PARA MOVERSE THE MENUS POR LOS MENUS TECLA ESCAPE ESCAPE KEY...
Page 94
Digital fire detection control panel LYON REMOTE PLUS 3.3-Configure Loop By selecting option 1 Loop Configuration the option will be the first to appear. Confirm with the ENTER key. You will be asked for the number of the loop to be configured.
Page 95
Digital fire detection control panel LYON REMOTE PLUS 3.5.-Assign a number to Point Confirm with the ENTER key.(Menu(code 27) 4.-System setup (code 9000) 2.-Configure1.Loop configuration3.-Set up Loop Points 3.- Assign Point number) This option assigns a loop and an order number within the loop to each element.
Page 96
Digital fire detection control panel LYON REMOTE PLUS L o o p 0 0 1 P o i n t 0 0 3 A 3 0 X H A L o o p 0 0 1 P u n t o : 0 0 1 S .
Page 97
NOTE: COFEM S.A. reserves the right to make changes due to typographical errors, inaccuracies in the current information or program and/or equipment improvements at any time and without prior notice. FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I.
Page 99
__________________________________________________________________ __________________________________________________________________ __________________________________________________________________ NOTE: __________________________________________________________________ COFEM S.A. reserves the right to make changes due to typographical errors, inaccuracies in the current information or program and/or __________________________________________________________________ equipment improvements at any time and without prior notice. __________________________________________________________________ FIRE PROTECTION MANUFACTURER C / Compositor Wagner, 8 –P.I. Can Jardí 08191 - RUBÍ (Barcelona) ESPAÑA.