Continued
Table 2-5 describes the I/O connectors on the 565-256 Power I/O Interface PCB
Assembly (refer to Figure 2-5 for the location of these connectors).
Table 2-5. 565-256 Power I/O Interface PCB Assembly I/O
Label
Description
P1
Power Module Supervision Interface (PMSI) Interface
P2 & P3
Mapnet Power and 36V Converter Trouble Signal Output
P4
5V & 28V System Power Output To Standard Slave Card
P5
Battery Supervision Jumper (1-2 battery, 2-3 no battery)
P6
Trickle Adjust - NICAD
P7
Connection For Current Limit Resistor 1
P8
Connection For Current Limit Resistor 2
P9
Interface To Power Supply (PS Status & Control / 28UPS)
P10
B-tap Enable
P11
Unswitched Tap Enable
P12
A-tap Enable
P13
NiCad Trickle Adjust
P14
C-tap Enable
J1
Standard Slave Interface Connector
TB1
Option Interface
TB2
A-tap Output Connections
TB3
B-tap Output Connections
TB4
C-tap Output Connections
R139
Battery Load resistor
Power Cable Connections: Red +28V / Black 0V / Yellow Charger
Table 2-6 describes the I/O connectors on the 565-220 Power I/O Interface PCB
Assembly (refer to Figure 2-6 for the location of these connectors).
Table 2-6. 565-220 Power I/O Interface PCB Assembly I/O
Label
Description
P1
Standard Slave Interface Cable
P2
5V & 28V System Power Output To Standard Slave Card
P3
Unswitched tap Enable
P4
A-tap Enable
P5
A-tap In
P6
B-tap Enable
P7
B-tap In
P8 & P9
Mapnet Power and 36V Converter Trouble Signal Output
TB1
A & B Tap Connections
J1
Supply Control & Monitor Connections To Power Supply
J2
Supply AC Monitor / 24UPS Connections To Power Supply
2-11
Connectors
Connectors

Hide quick links: