ICP DAS USA GT-530 User Manual page 29

Intelligent sms alarm controller
Table of Contents

Advertisement

(1)
SMS command: Authority to send the SMS commands to GT-530
(2)
Time Report: Authority to receive the counter SMS report periodically.
(3)
Event Report: Authority to receive the event SMS report
4.
Counter Report (Time report)
(1)
Enable Counter Report: Enable the function in this item.
(2)
Report Interval : The time interval for counter report and it is set by day
(1 ~ 31 )
(3)
Report time:Hour/Minute/Second
Note: The SMS format of counter report is fixed. It can not be modified by
users:
CRPT;Machine ID;Report Date;Report Time;DI0;DI1;DI2;DI3;DI4;DI5
Text field:
CRPT:Counter report
Machine ID:GT-530 ID
Report Date:Report date (The format is YYYYMMDD (YYYY=year,
MM=month, DD=day))
Report Time: Report time (The format is HHMMSS (HH=hour,
MM=minute, SS=second))
DI0 ~ DI5: The counter values of DI0 ~ DI5.
If these DI channels are not set as counter mode, the counter value would be zero
Note:
If CRPT function is enabled and the return time is changed, the next time to
send the SMS report is re-calculated according to the current time of GT-530
and the CRPT time. There would 2 conditions on the day:
(1) When the GT-530 time is over the CRTP time, GT-530 would send the
CRTP SMS after 1 minute.
(2) If the GT-530 time does not reach the CRTP time, GT-530 would not send
the CRTP SMS until GT-530 time reaches the CRTP time.
5.
Power Down Alarm
The function supports to send alert SMS when the external power is off.
The alert time after the event happened can be set by minutes (0 ~ 60
minutes).
6.
Low Battery Volume Alarm
The function supports to send alert SMS when the volume of battery is low.
The low battery value can be set as 10%~ 50% less than total volume.
GT-530 User Manual, Version 1.0, August 2009
GT-530 user manual v1.0
25/48