ABB ACS2000 User Manual page 175

Medium voltage drives
Hide thumbs Also See for ACS2000:
Table of Contents

Advertisement

9.3.5.2 Drive selection procedure
1
To enter the drive
mode, press the
DRIVE key.
2
To connect the CDP
control panel to the
AFE, press either of
the slow navigation
keys to select the ID
number of the AFE.
ACS2000 User manual
Note: It is assumed in the following example that the CDP control panel is
connected to the INU.
If none of the keys is pressed, the display will automatically return to the
actual signal display mode after a while.
If the ID number of the AFE or INU is accidently changed (e.g. to 3) and
the ENTER key has been pressed, the new number will be saved in the
memory. The display will still show the old number. Only when the auxiliary
voltage has been switched off and on again, will the new number be shown
on the display.
If the ID number is accidently changed, simply change the ID number back
and press the ENTER key. The ID number will be restored the next time
the auxiliary power is switched off and on.
Note: DO NOT select LOCAL by pressing
the LOC / REM key when the CDP control
panel is connected to the AFE. If the drive is
in operation, the AFE will stop modulating
and the drive will shut down. If the drive is
stopped and the CDP control panel is set to
LOCAL, the drive cannot be started up.
2UEA001270 Rev. F
Chapter 9 - CDP control panel
ACS2000AD
4k SingleINU
LDAI5500
1
ID-Number
ACS2000AFE
4k SingleAFE
LBAI5120
ID-Number
2
LOC/REM key
9-19 (24)