ABB ACS2000 User Manual page 140

Medium voltage drives
Hide thumbs Also See for ACS2000:
Table of Contents

Advertisement

Chapter 8 - Local operation
Legend
1
CDP control panel*
2
SUPPLY OFF
/ DISCHARGING
pushbutton
/ pilot light
3
SUPPLY ON
/CHARGING
pushbutton
/ pilot light
4
FAULT/ALARM
pilot light
5
GROUND SW RELEASED
pilot light
6
Emergency OFF
pushbutton
* See Chapter 9 - CDP control panel for further information on the CDP control panel.
Figure 8-1
Local operator panel functions
8-2 (18)
5
6
-
Starts and stops the motor
Displays status messages of AFE (Active Front
End) and INU (INverter Unit)
Displays alarm/fault messages of the drive and
monitored equipment
green
Discharging - opens the MV switchgear and
light
initiates discharge of the DC link
Solid on: DC link discharged
Flashing: charging or discharging
white
Charges the DC link and closes the MV switchgear
light
Flashing: charging or discharging
Solid on: DC link energized (MV switchgear
closed)
blue
Flashing: alarm
light
Solid on: fault
yellow
Solid on: indicates that the grounding switch can
light
be turned
-
Removes power when pressed:
MV switchgear opens immediately and DC link
discharges
Motor coasts to a stop
2UEA001270 Rev. F
1
2
3
4
ACS2000 User manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents