Tightening torque
6.6.3.4 Fuses
Figure 6-11 Check power fuses
ACS2000 User manual
Figure 6-10 Typical busbar connections
Tighten bolted connections with bolts of sizes M12 or 1/2 inch and greater
with the recommended nominal torque for the bolt size used. See
Table 6-2 for torque values.
Raised
Flush
Good
Blown
Fuse condition
Site window detail
(Behind swing frame)
Check that the power fuses are securely bolted and torqued in place.
Torque value is 20 Nm [15 ft-lbs]. Check that the electrical wires are
attached to both ends of the fuses. Make sure the fuses are not blown. The
red indicator pin should be flush with the top of the fuse. See Figure 6-11.
If one fuse has blown, the other fuses may be degraded. ABB
recommends that all fuses be replaced.
2UEA001270 Rev. F
Chapter 6 - Electrical installation
Legend
1
Red indicator pin
2
Fuse
1
2
6-13 (16)