Input Modules; Output Modules - Honeywell NOTIFIER AM1000 Programming Manual

Hide thumbs Also See for NOTIFIER AM1000:

Advertisement

Sumarizing Type ID for modules tables

INPUT MODULES

WIRING

OUTPUT MODULES

Abbrevation
CON
FORC
UTPUT MODULES FOR GENRAL SIGNALS
Abbrevation
PWRC
CMX-2
Control module used to momentarily interrup power (druring the SYSTEM RESET) of conventional
4-wire smoke detectors, powered from a remote main power supply (FORC).
NOTE : this module CANNOT be programmed for SIGNAL SILENCE.
Control module configured as a Form-C relay, which will be activated whenever an alarm or a trouble
GPND
conditions occurs.
It will be reset via ACK operation.
AM-1000
AM1000_manu
ABBREVIATION
MON3
MMX-1 Monitor Module
Monitor Module used to monitor N.O. Contacts.
Comlpies EN54
MON
MMX-1 Monitor Module
Monitor Module used to monitor N.O. Contacts.
NOT Comlpies EN54
SCON
MMX-2 Monitor Module
Monitor Module used for convetional 4-wire smoke detectors, not detected
durinig autoprogramminig.
NOTE: this module has a reset time longer than modules programmed
as "MONITOR".
SCO2
It is valid for ZM2 module to connect conventional detectors.
It is automatically detected during the autoprogramming.
NONA
MMX-1 Monitor Module
Monitor Module used to monitor N.O. Contacts , with alarm signal as
soon as the contact is closed. Activation of a module with Type_id "NONA"
Will not cause an alarm condition i.e. :
- Aarm LED will not illuminate ;
- on the CRT-1 terminal status line , no alarm will be added;
- modules with Type-ID "APND" or "GPND" will not activated
Only the control modules mapped to CBE will be activated
PULL
As for MON Type-ID , used for Call Points.
STAT
Monitor Module used as NONA Type-ID, but every status change will be
Indicateted on the printer .
NCMN
Monitor Module used to monitor N.C. Initiating devices.
Line wire cut will be indicatted as Alarm.
Line short circuit will be indicated as Trouble.
Control Module used to monitor of connection towards devices.
Control Module with relay contacts not supervised (free from potential).
Programming manual
Doc. M-145.2-AM1000-ENG Rev A.1
Type of Device
Type of Device
CMX-2
CMX-2
Type of Device
Page 21
NOTIFIER ITALIA