Is the user who denies the operand or the serie of in brackets following operands
Example: the equation of a CMX-2 module is: NOT (G23).
The CMX-2 will remain active till the operando (G23) will not be in alarm:
- IF the software group 23 is in alarm
- THEN this CMX-2 will be deactivated.
Is the user who need at least two elements of the followed indicated group are active.
FORMAT : XGRP (GXXX)
Example: the equation of a CMX-2 module is: XGRP (G23)
- IF ANY COMBINATION of two or more input devices (detectors or modules), that have been programmed
(with their CBE Equation) on this software group, are activeI.
- THEN this CMX-2 will be activated.
Is the user who allows to programm the delays of activation for fixed conditions.
The device that has in his CBE equation the user "DEL", when the equation becomes true waits for the
programmed time to be activated.
If during this delay time his equation is not true, the timer is resetted and it is ready to start again for the next
causing event (the output device is not activated).
FORMAT : DEL (MM.SS (delay) MM.SS. (lenght - opzional) (CONDITION) equation that fix the beginning
of the delay)
Where:
MM = minuts (2 numbers), SS = seconds (2 numbers)
CONDITION = can be an equation like:
Element = can be GXXX for a group (1-100) - LXX S/MXX for an addressable point
Example 1: if the equation of the software group G90 is DEL (00.30 01.30 (G21)):
- After 30 Sec. From the activation of G21
- the group G90 will be activated and will remain activated for 1 minut and 30 seconds
AM-1000
AM1000_manu
XGRP
where G= Group 1-100
XGRP (GXXX)
NOT (Element 1...)
OR (Element 1...Element 2...)
AND (Element 1...Element 2..)
Programming manual
Doc. M-145.2-AM1000-ENG Rev A.1
NOT
DEL
Page 37