Tesla 1069742-00-A Installation Manual page 21

Wall connector, 80a single phase
Table of Contents

Advertisement

Step-by-Step Installation Instructions
4.
Lead the preconnected service wires in
the main housing 3/8" (10 mm) and
connect the preconnected service wires to
the terminal block with L1 (or line), L2 (or
neutral), and ground wires going to the
locations shown in the following
illustration.
Caution: Cut each of the wire strands
and insert them fully into each the
terminal block.
Note: To ensure proper operation, verify
that neutral is connected to the neutral
line inside the circuit breaker box or the
main electrical panel.
5.
Tighten the terminal block to the
recommended torque:
35 in-lb (4.0 N-m) for the terminal
block on the top entry bracket.
33 in-lb (3.8 N-m) for the terminal
block in the main housing.
18 in-lb (2.0 N-m) for the ground
terminal block in the main housing.
6.
Check for miswiring using a multimeter
and verify that there are no shorts before
turning the upstream circuit breaker ON.