LXL-1010 Installation and Setup Guide
Zone Sounds & Timing ( ∗ ∗ ∗ ∗ 31– ∗ ∗ ∗ ∗ 39)
FIELD
TITLE and DATA ENTRIES
Single Alarm Sounding Per Zone
*31
(per armed period)
0 = no limit on alarm sounding per zone
1 = limit alarm sounding to once per
Fire Alarm Sounder Timeout
*32
0 = yes; fire sounder timeout after time
1 = no fire sounder timeout; continue
Alarm Sounder Timeout
*33
0 = No timeout
1 = 4 min
2 = 8 min
Exit Delay
*34
00 - 96 = 0 - 96 seconds
97 = 120 seconds
Entry Delay 1
*35
00 - 96 = 0 - 96 seconds
97 = 120 seconds
98 = 180 seconds
99 = 240 seconds
Entry Delay 2
*36
See *35 above for entries.
Audible Exit Warning
*37
0 = no; 1 = yes
Confirmation Of Arming Ding
*38
0 = no ding
1 = confirmation ding after arming system
2 = confirmation ding after arming from
Power-Up In Previous State
*39
0 = always power-up in a disarmed state
1 = assume the system status prior to
4–2
www.PDF-Zoo.com
arming period for a given zone
programmed in field ∗33
sounding until manually turned off
3 = 12 min
4 = 16 min
RF button or RF keypad only
power down
firealarmresources.com
EXPLANATION
Note: This field applies to the internal sounder only.
UL installations must be 0 (no limit).
This control complies with NFPA requirements for temporal pulse
sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
UL fire alarm installations: must be 1.
This field determines whether the sounder will shut off after time
allotted, or continue until manually turned off.
UL installations: For residential fire alarm installation, must be set
for a minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4).
The system waits the time entered before arming entry/exit zones. If
the entry/exit door is left open after this time expires, an alarm will
occur.
UL installations: For UL Commercial Burglar Alarm (Grade AA) and
UL Residential Burglar Alarm installations with line security, total
exit time must not exceed 60 seconds. For UL Burglar Alarm
installations without line security (Grade A), total exit time must not
exceed 120 seconds.
SIA Installations: minimum exit delay is 45 seconds
Upon entering, the system must be disarmed before the time entered
expires, otherwise it sounds an alarm.
UL installations: For UL Residential Burglary Alarm installations,
must be set for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm, total
entry delay may not exceed 45 seconds.
SIA Installations: minimum entry delay is 30 seconds
See *35 above for explanation.
Warning sound consists of slow continuous beeps until last 10 seconds,
then it changes to fast beeps. Sound ends when exit time expires.
SIA Installations: must be enabled (enter 1)
Confirmation of arming is 1/2 second internal sounder "ding." When
enabled, ding will occur at the end of exit time, or after closing report
has been sent (if programmed).
If "1" selected, ding occurs when closing report is sent, or at the end of
Exit Delay.
If "2" selected, ding occurs upon reception of the wireless arming
command.
UL installations: must be "1" for UL Commercial Burglar Alarm
installations.
When the system powers up armed, an alarm will occur 1 minute
after arming if a zone is faulted.
Note that if the previous state was armed Away or Stay, the system
will not respond to sensor changes for 1 minute, which allows time for
sensors such as PIRs to stabilize.
UL installations: must be 1 (power-up in previous state)