EXIT Options
*88
0 = standard *98 installer code lockout
1 = lockout [∗] + [#] reentry after *98 exit
2 = not used
3 = lockout all local programming after *98
Event Log Full Report Code
*89
0 = no report
1-F = see description above *59
Event Log Enables
*90
0 = no event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of
Option Selection
*91
0 = none
4 = none
8 = Enable Exit delay restart/reset ††
FOR SIA INSTALLATIONS: Exit delay
should be enabled.
FIELD
TITLE and DATA ENTRIES
Phone Line Monitor Enable
*92
Entry 1–Timeout:
0 = disabled
1-15 = 1 minute to 15 minutes respectively
(2 = 2 min, 3 = 3 min, etc.; # + 10 =10 min,
# + 11 = 11 min, # + 12 = 12 min, # + 13 =
13 min, # + 14 = 14 min, # + 15 = 15 min)
Entry 2–Display/Sound:
0 = keypad display only when phone line
1 = keypad display plus keypad trouble
2 = Same as "1" plus programmed output
No. of Reports In Armed Period
*93
per Zone (Swinger Suppression)
0 = unlimited number of reports
1 = 1 report per zone per armed period
2 = 2 reports per zone per armed period
Download Information (*94, *95)
Download Phone Number
*94
Enter up to 20 digits as follows: 0–9, # +11
for "∗", # + 12 for "#", # + 13 for a pause.
www.PDF-Zoo.com
(reentry via installer code only)
exit (reentry via downloader only)
entries)
is faulted.
sound when line is faulted. No
automatic timeout.
device STARTS. If the system is
armed, external sounder activates.
External sounder will be turned off by
normal alarm sounder timeout, or by
security code plus OFF.
firealarmresources.com
Section 4: Data Field Programming
Select the desired options. The following table summarizes the
Program mode lockout options:
Exit
*88
Reentry By:
Command Entry Installer
*99
n/a
yes
*98
0
no
*98
1
yes
*98
3
no
† pressing [∗] + [#] within 50 seconds of power up
If an Event Logging selection is made in field ∗90, a message can
be sent to the central station receiver when the log is 80% full. If
the log becomes full, new messages overwrite the oldest messages
in the log.
This system has the ability to record up to 50 events in a history
log. At any time, the downloader operator can then upload the log
and view or print out all or selected categories of the log. The
downloader operator can also clear the log. Event log can also be
viewed at an alpha keypad.
The display/printout at the central station will show the date,
time, event, and description of the occurrences.
Data Entry Example: To select Alarm/Alarm Restore" and
"Open/Close", enter 9 (1+ 8); to select all events, enter #15.
Select the desired options by adding the values of each desired
option.
††"Exit Delay Restart/reset" option allows use of the [∗] key to
restart the exit delay at any time when the system is armed STAY
or INSTANT. This feature also enables automatic exit delay reset,
which resets exit delay if the entry/exit door is re-opened before
exit delay time expires after arming AWAY.
EXPLANATION
Entry 1: Sets the length of time a phone line fault must remain after
detected before the second digit option is activated.
Entry 2: Selects the desired phone line fault response.
Option 2 may be used even if a relay unit or Powerline carrier device
is not connected to the control.
Programmed Output Device must either be programmed to be
STOPPED in field ∗80 or STOPPED by entry of [security code] + [#] +
8 + device number.
U L
Field *92 must be enabled for fire alarm installations, UL
commercial burglar alarm installations and UL residential burglar
alarm installations.
If the control unit is used on a UL commercial burglar alarm
system that requires 2 methods of remote communication, then the
control unit's DACT and the other method of signal transmission
must monitor each other against communication failure and line
fault. The fault must be received and annunciated within 200
seconds of its occurrence.
This option can be used to limit the number of alarm/alarm restore
messages per zone sent to the central station in an armed period.
UL installations must be 0 (unlimited reports).
Used for downloader callback connect or site initiated download.
Enter the phone number of the downloading computer.
Do not fill unused spaces. End field by entering ∗. To clear entries
from field, press ∗94∗.
Power-up† Downloader
yes
yes
yes
yes
no
yes
no
yes
4–7