Play Announcements On Specific Floors; Listen To What Is Being Played On The Evac Channel Using The Local Speaker; Listen To What Is Being Played On The Alert Channel Using The Local Speaker; Silencing The Audio System - Simplex 4100U Operator's Manual

Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Three to Eight Channel Audio System Operation,
Play
Announcements on
Specific Floors
Listen to What is
Being Played on the
EVAC Channel
Using the Local
Speaker
Listen to What is
Being Played on the
Alert Channel Using
the Local Speaker
Silencing the Audio
System
Resetting the Audio
System
Technical Manuals Online! - http://www.tech-man.com
Multi channel audio systems have the capability to play specific announcements on specific floors.
To do this, follow these steps.
1. Press the button corresponding to the floors.
2. Press the Start All Selected button.
When you do this, the LEDs on the display card light and the announcement plays over the
speakers.
1. Press the button labeled "Local Speaker" to hear what is being played on the EVAC channel
at that time. The LED associated with this button illuminates when the button is pressed to
indicate the function is active.
Note: If the user picks up the local phone or keys the microphone while the local speaker is
active, the speaker shuts off to prevent feedback. The local speaker turns back on when the
page is complete.
1. Press the button labeled "Local Speaker Alert" to hear what is being played on the Alert
channel at that time. The LED associated with this button illuminates when the button is
pressed to indicate the function is active.
Note: If the user picks up the local phone or keys the microphone while the local speaker is
active, the speaker shuts off to prevent feedback. The local speaker turns back on when the
page is complete.
Press the Alarm Silence button on the front panel to silence the audio system. When you do this,
the speakers remain on, but play nothing.
Press the System Reset button to reset the audio system. When you do this, the following occurs.
All speakers and associated LEDs turn OFF.
The local speaker turns off.
Any paging that is in progress is canceled.