Evacuate Entire Building; Evacuate Specific Floors When No Alarms Are Present; Evacuate Additional Floors During An Alarm; Alert Specific Floors - Simplex 4100U Operator's Manual

Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Two Channel Audio Operation,
Evacuate Entire
Building
Evacuate Specific
Floors when No
Alarms are Present
Evacuate Additional
Floors During an
Alarm

Alert Specific Floors

Technical Manuals Online! - http://www.tech-man.com
Continued
1. Press the All Speakers Evac button to play the evacuation message on every speaker circuit
connected to the audio system.
To indicate that the All Speakers Evac function has been activated, the LED associated with
this button illuminates, as do the LEDs for each of the speaker circuits (floors).
Specific floors in the building can be manually evacuated at any time, even when no fire alarm
condition is present. To do this, follow these steps.
1. Press the speaker circuit buttons corresponding to the speaker groups (floors) you want to
evacuate. The LEDs corresponding to the selected speaker groups illuminate.
2. Press the Selective Evac button. The LED associated with the Selective Evac button
illuminates and the Primary Evacuation message plays on the selected speaker circuit.
Example
To evacuate floors 1 and 2, you would first press the buttons labeled Floor 1 and
Floor 2. Their LEDs light to let you know that these are the selected floors. Next,
press the Selective Evac button. The Selective Evac LED lights and the message
plays on the selected floors.
When a fire alarm occurs, the evacuation message automatically plays on specific floors but other
floors (or areas) of the building may not automatically play the message. Additional floors can be
evacuated, as follows:
1. Press the speaker circuit button(s) for the additional floors. When you do this, the LEDs for
the selected floors illuminate and the message automatically plays on the speaker circuits for
those floors.
Note:
The evacuation message begins at whatever point it is currently at. For example, the
entire message may be, "Please evacuate this Floor. Proceed to your designated assembly
area." If you press the speaker circuit when the message is half through, only the second half
of the message will play on the additional speaker circuit.
Follow these steps to play the Alert message on specific floors (areas) of the building.
1. Press the speaker circuit buttons corresponding to the speaker groups (floors) on which you
want to play the Alert message. The LEDs corresponding to the selected speaker groups
illuminate.
2. Press the Selective Alert button. The LED associated with the Selective Alert button
illuminates and the Alert message plays on the selected speaker circuit.
firealarmresources.com
8-8
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents