1. Press the All Speakers Talk button. The LED associated with this button illuminates, along
with the LEDs for each of the speaker circuits.
2. Key the microphone (depress the talk switch) and wait for the Ready to Talk LED to
illuminate. When this LED is ON, talk into the microphone. The page is routed to all speaker
circuits connected to the system.
1. Press the buttons corresponding to the floors requiring the page. The LEDs associated with
the selected buttons illuminate.
2. Key the microphone (depress the talk switch).
3. Wait for the Ready to Talk LED to illuminate and speak into the microphone to page the
floors selected in Step 1.
While a page is in progress, you can add floors to the existing page. To do this, follow these steps.
1. Press the buttons associated with the additional floors. The LEDs associated with these floors
turn ON and the page is heard on their speaker circuits
1. Press the button labeled "Local Speaker" to hear what is being played on the EVAC channel
at that time. The LED associated with this button illuminates when the button is pressed to
indicate the function is active.
Note: If the user picks up the local phone or keys the microphone while the local speaker is
active, the speaker shuts off to prevent feedback. The local speaker turns back on when the
page is complete.
Press the Alarm Silence button on the front panel to silence the audio system. When you do this,
the speakers remain on, but play nothing.
Press the System Reset button to reset the audio system. When you do this, the following occurs.
All speakers and associated LEDs turn OFF.
The local speaker turns off.
Any paging that is in progress is canceled.