Truealert Appliance Walktest; Procedure - Simplex 4100 Operation

Front panel
Hide thumbs Also See for 4100:
Table of Contents

Advertisement

TrueAlert Appliance WalkTest

Procedure

Notes:
1. In order for the TrueAlert Appliance WalkTest to work properly,
only one VNAC is allowed per WalkTest group.
2. The TrueAlert strobes will not flash during this test.
The TrueAlert Addressable Controller will fully support the Non-Voice Simplex
WalkTest. Use the following procedure to initiate the TrueAlert WalkTest.
1.
Put the 4100/4020 Operator Interface Panel into WalkTest and verify the
WalkTest trouble reports.
2.
Initiate a monitor point from each WalkTest group and verify that the
correct code is generated on the appropriate appliance.