How To Enable A Vnac - Simplex 4100 Operation

Front panel
Hide thumbs Also See for 4100:
Table of Contents

Advertisement

Handling Disabled Conditions,

How to Enable a VNAC

Continued
Note:
To perform this procedure, you must be at the correct Access
Level or higher.
Use the following procedure to enable a VNAC:
1.
Press <TBL ACK> until the VNAC signal number is displayed.
VIRTUAL NAC 10 – ALL A/V DEVICES
SIGNAL CIRCUIT
2.
Press ENABLE.
PRESS <ENTER> TO ENABLE
SIGNAL CIRCUIT: SIG12
3.
Press ENTER on the ENTRY keypad. The display acknowledges the
action.
ACTION TAKEN
The trouble count should decrease by one.
4.
After a few seconds, a message appears. (For this example, the signal circuit
is "OFF.")
VIRTUAL NAC 10 – ALL A/V DEVICES
SIGNAL CIRCUIT
Enable the remaining VNAC in a similar manner.
2-6