Safety

Electrical safety precautions

These electrical safety precautions are for all personnel who do work on the drive, motor
cable or motor.
WARNING!
Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
If you are not a qualified electrical professional, do not do installation or
maintenance work.
Go through these steps before you begin any installation or maintenance work.
1.
Clearly identify the work location and equipment.
2.
Disconnect all possible voltage sources. Make sure that re-connection is not possible.
Lock out and tag out.
Open the main disconnecting device of the drive.
Open the charging switch if present.
Open the disconnector of the supply transformer. (The main disconnecting device
in the drive cabinet does not disconnect the voltage from the AC input power
busbars of the drive cabinet.)
If the drive is equipped with a DC/DC converter unit (optional) or a DC feeder unit
(optional): Open the DC switch-disconnector ([Q11], option +F286 or +F290) of the
unit. Open the disconnecting device of the energy storage connected to the unit
(outside the drive cabinet).
Open the auxiliary voltage switch-disconnector (if present), and all other possible
disconnecting devices that isolate the drive from dangerous voltage sources.
Safety 7