Group 9: Communication Parameters
09 - 00

Communication Address

Settings
If the AC drive is controlled by RS-485 serial communication, the communication address for
this drive must be set via this parameter.
09 - 01

Transmission Speed (Baud Rate)

Settings
This parameter determines transmission speed of AC drive communication.
09 - 02

Transmission Fault Treatment

Settings
This parameter is set to detect if an error occurs and take actions.
09 - 03

Time-out Detection during Transmission

Settings
This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the
time-out detection is enable, the time slot between each character can't exceed 500 ms.
09 - 04
Communication Format
Settings
Revision July 2008, EG03, SW V1.06
01-254
00: Disabled
00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400
00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display
00: Disabled
01: Enabled
00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU
Chapter 4 Parameters|
Factory Setting: 01
Factory Setting: 01
Factory Setting: 03
Factory Setting: 00
Factory Setting: 00
4-69