Rated Slip Frequency Of Motor; Auto Torque Compensation Gain; Torque Compensation Gain By Manual Operation - Delta Electronics AC Motor Drive VFD-G User Manual

Vfd-g series specific ac motor drives for plastic molding and air compressors machinery
Table of Contents

Advertisement

Chapter 4 Parameters|
07 - 05

Rated Slip Frequency of Motor

Settings
This parameter is to set rated slip of loaded motor. Users need to input rated rotation speed
according to nameplate of loaded motor. If rated frequency of motor is 60Hz, number of motor
poles is 4 and rated rotation speed of motor is 1650rpm. The rated slip frequency of motor is
60Hz-(1650rpm X 4/120) = 5Hz.
This parameter has relation with 07-04 slip compensation. To have the best slip compensation,
this parameter must be set correctly. Incorrect setting may cause above functions disable and
even damage the motor and AC drive.
07 - 06

Auto Torque Compensation Gain

Settings
This parameter is to set auto torque compensation gain.
When motor loading is high, a part of output frequency of AC drive will be absorbed by
impedance of stator winding to make voltage of exciting inductance of motor is not enough.
Therefore, the short of gap magnet field will make a high output current but low output torque.
Auto torque compensation gain could adjust output voltage automatically according to loading
to maintain in a fixed gap magnet of the motor to get the best running situation.
If the setting of compensation gain is too great, over-exciting magnet will cause the following
situation: output current of AC drive is too great, motor is over-heating or protection function
occurs.
07 - 07

Torque Compensation Gain by Manual Operation

Settings
This parameter determines torque compensation gain by manual operation.
Torque compensation gain by manual operation won't refer to the loading situation and adds
compensation voltage on the setting V/f curve. Basically, it just changes V/f curve. It could be
reached by adjusting V/f curve.
07 - 08
Calculate Total Running Time of the Motor (Min)
Settings
07 - 09
Calculate Total Running Time of the Motor (Day)
Settings
4-60
0.00~20.00Hz
0.0~10.0
0.0~10.0
00 to 1439 Min
00 to 65535 Day
Factory Setting: 0.00
Factory Setting: 0.0
Factory Setting: 0.0
Factory Setting: 00
Factory Setting: 00
Revision July 2008, EG03, SW V1.06
Unit: 0.01
Unit: 0.1
Unit: 1.0
Unit: 1
Unit: 1