Table 18A — Example of Configuring Dual Chiller Control
(Master Chiller)
ITEM
DISPLAY
CRST
0
LLDY
5
5
5
10
10
LLDY
10
LLBD
168
LEAD/LAG BALANCE DELTA
LLBL
DSBL
LEAD/LAG BALANCE SELECT
DSBL
DSBL
ENBL
ENBL
LLBL
ENBL
SLVA
0
0
0
6
6
SLVA
6
MSSL
MAST
Table 18B — Example of Configuring Dual Chiller Control
(Slave Chiller)
ITEM
DISPLAY
CRST
0
LLDY
5
LLBD
168
LEAD/LAG BALANCE DELTA
LLBL
DSBL
LEAD/LAG BALANCE SELECT
SLVA
0
MSSL
MAST
MAST
MAST
SLVE
SLVE
MSSL
LLEN
DSBL
LEAD/LAG CHILLER ENABLE
DSBL
DSBL
ENBL
LLEN
ENBL
LLEN
ENBL
LEAD/LAG CHILLER ENABLE
ITEM EXPANSION
COOLING RESET TYPE
LAG START DELAY
Scrolling stops
Value flashes
Select 10
Change accepted
No change needed. Default set for weekly changeover
Scrolling stops
Value flashes
Select Enable
Change accepted
SLAVE ADDRESS
Scrolling stops
Value flashes
Select 6
Change accepted
No change needed. Default set for Master
MASTER/SLAVE SELECT
ITEM EXPANSION
COOLING RESET TYPE
LAG START DELAY
No change needed. Default set for weekly changeover
SLAVE ADDRESS
Default set for Master
MASTER/SLAVE SELECT
Scrolling stops
Value flashes
Select SLVE
Change accepted
Item/Value/Units scrolls again
Scrolling stops
Value flashes
Select enable
Change accepted
Item/Value/Units scrolls again
39
COMMENT
COMMENT