Carrier Air Conditioner Operation And Service Manual page 32

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

KEYPAD
SUB-MODE
ENTRY
TEST
ENTER
OUTS
ENTER
COMP
ENTER
LEGEND
EXV — Electronic Expansion Valve
Table 9 — Service Test Mode and Sub-Mode Directory
ITEM
RANGE
TEST
OFF-ON
LLS.A
OPEN-CLSE
EXV.A
0 - 100%
LLS.B
OPEN-CLSE
EXV.B
0 - 100%
FAN1
OFF-ON
FAN2
OFF-ON
FAN3
OFF-ON
FAN4
OFF-ON
CLR.P
OFF-ON
CND.P
OFF-ON
RMT.A
OFF-ON
CC.A1
OFF-ON
CC.A2
OFF-ON
CC.A3
OFF-ON
CC.A4
OFF-ON
UL.A1
OFF-ON
UL.A2
OFF-ON
HGBP
OFF-ON
CC.B1
OFF-ON
CC.B2
OFF-ON
CC.B3
OFF-ON
CC.B4
OFF-ON
UL.B1
OFF-ON
UL.B2
OFF-ON
ITEM EXPANSION
SERVICE TEST MODE
LIQ. LINE SOLENOID VALVE
EXV % OPEN
LIQ. LINE SOLENOID VALVE
EXV % OPEN
FAN 1 RELAY
FAN 2 RELAY
FAN 3 RELAY
FAN 4 RELAY
COOLER PUMP RELAY
CONDENSER PUMP RELAY
REMOTE ALARM RELAY
COMPRESSOR A1 RELAY
COMPRESSOR A2 RELAY
COMPRESSOR A3 RELAY
COMPRESSOR A4 RELAY
UNLOADER A1 RELAY
UNLOADER A2 RELAY
HOT GAS BYPASS RELAY
COMPRESSOR B1 RELAY
COMPRESSOR B2 RELAY
COMPRESSOR B3 RELAY
COMPRESSOR B4 RELAY
UNLOADER B1 RELAY
UNLOADER B2 RELAY
32
COMMENT
Use to Enable/Disable Manual Mode
TXV units only
TXV units only
Fan 3: (040-050)
Fans 3, 4: (060-110, 230B-315B)
Fans 1, 2: (130 [60 Hz])
Fans 1: (130 [50 Hz], 150, 170,
230A-270A, 330A/B, 360B [50 Hz])
Fans 1, 11: (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
Fan 4: (040-050)
Fans 5, 6: (060-090, 230B-245B)
Fans 5, 6, 7, 8: (100, 110, 255B-315B)
Fans 3, 4, 9, 10: (130 [60 Hz])
Fan 2: (130 [50 Hz], 150, 170,
230A-270A, 330A/B, 360B [50 Hz])
Fans 2, 12: (190-210, 290A, 315A,
360A, 360B [60 Hz], 390A/B-420A/B)
Fans 3, 9: (130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)
Fans 4, 10: (130 [50 Hz], 150-210,
230A-315A, 330A/B-420A/B)