Carrier Air Conditioner Operation And Service Manual page 44

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

KEYPAD
MODE
ENTRY
ENTER
CONFIGURATION
The following are examples of outdoor air and space tem-
perature resets:
LEGEND
LWT — Leaving Water (Fluid) Temperature
Table 26 — Configuring Temperature Reset
KEYPAD
SUB-MODE
ITEM DISPLAY
ENTRY
DISP
TEST
ENTER
UNIT
TYPE
ENTER
OPT1
FLUD
ENTER
OPT2
CTRL
ENTER
RSET
CRST
ENTER
CRT1 XXX.X F
CRT2 XXX.X F FULL COOL RESET TEMP
DGRC XX.X °F
ITEM
EXPANSION
ON/OFF
TEST DISPLAY LEDS
UNIT TYPE
COOLER FLUID
CONTROL METHOD
COOLING RESET TYPE
NO COOL RESET TEMP
DEGREES COOL RESET
LEGEND
LWT — Leaving Water (Fluid) Temperature
44
COMMENT
0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8)
3 = Return Fluid
4 = Space Temperature (Connect to
TB5-5,6)
Default: 125 F (51.7 C)
Range: 0° to125 F
Set to 4.0 for CRST= 1
Default: 0° F (–17.8 C)
Range: 0° to 125 F
Set to 20.0 for CRST=1
Default: 0° F (0° C)
Range: –30 to 30° F (–16.7 to 16.7° C)

Hide quick links: