Alarm And Alert Codes - Carrier Air Conditioner Operation And Service Manual

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

ALARM/
ALARM
ALERT
OR
DESCRIPTION
CODE
ALERT
T051
Alert
Circuit A, Compressor 1
Failure
T052
Alert
Circuit A, Compressor 2
Failure
T053
Alert
Circuit A, Compressor 3
Failure
T054
Alert
Circuit A, Compressor 4
Failure
T055
Alert
Circuit B, Compressor 1
Failure
T056
Alert
Circuit B, Compressor 2
Failure
T057
Alert
Circuit B, Compressor 3
Failure
A060
Alarm
Cooler Leaving Fluid
Thermistor Failure (T1)
A061
Alarm
Cooler Entering Fluid
Thermistor Failure (T2)
T064
Alert
Circuit A Saturated Con-
densing Thermistor Failure
(T3)
T065
Alert
Circuit B Saturated Con-
densing Thermistor Failure
(T4)
T066
Alert
Circuit A Saturated Suction
Thermistor Failure (T5)
T067
Alert
Circuit B Saturated Suction
Thermistor Failure (T6)
T068
Alert
Compressor A1 Suction
Gas Thermistor Failure (T7)
T069
Alert
Compressor B1 Suction
Gas Thermistor Failure (T8)
T073
Alert
Outside Air Thermistor
Failure (T9)
T074
Alert
Space Temperature
Thermistor Failure (T10)
T077
Alert
Circuit A Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
T078
Alert
Circuit B Saturated
Suction Temperature
exceeds Cooler Leaving
Fluid Temperature
T079
Alert
Lead/Lag Thermistor Failure
Table 29 — Alarm and Alert Codes
WHY WAS THIS
ALARM
GENERATED?
Compressor feedback signal
Circuit A shut down.
does not match relay state
Compressor feedback signal
Circuit A shut down. Circuit
does not match relay state
restarted in 1 minute. Com-
pressor A2 not used until
alarm is reset.
Compressor feedback signal
Circuit A shut down. Circuit
does not match relay state
restarted in 1 minute. Com-
pressor A3 not used until
alarm is reset.
Compressor feedback signal
Circuit A shut down. Circuit
does not match relay state
restarted in 1 minute. Com-
pressor A4 not used until
alarm is reset.
Compressor feedback signal
Circuit B shut down.
does not match relay state
Compressor feedback signal
Circuit B shut down. Circuit
does not match relay state
restarted in 1 minute. Com-
pressor B2 not used until
alarm is reset.
Compressor feedback signal
Circuit B shut down. Circuit
does not match relay state
restarted in 1 minute. Com-
pressor B3 not used until
alarm is reset.
Thermistor outside range of
Chiller shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
Thermistor outside range of
Chiller shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
Thermistor outside range of
Circuit A shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
Thermistor outside range of
Circuit B shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
Thermistor outside range of
Circuit A shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
(EXV only)
Thermistor outside range of
Circuit B shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
(EXV only).
Thermistor outside range of
Circuit A shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
(EXV only).
Thermistor outside range of
Circuit B shutdown after
–40 to 245 F (–40 to 118 C)
pumpdown complete.
(EXV only).
Thermistor outside range of
Temperature reset disabled.
–40 to 245 F (–40 to 118 C)
Chiller runs under normal
control/set points.
Thermistor outside range of
Temperature reset disabled.
–40 to 245 F (–40 to 118 C)
Chiller runs under normal
control/set points.
Saturated suction is
Circuit A shutdown after
greater than leaving fluid
pumpdown complete.
temperature for more than
5 minutes
Saturated suction is
Circuit B shutdown after
greater than leaving fluid
pumpdown complete
temperature for more than
5 minutes
Thermistor outside range of
Lead/lag algorithm runs
–40 to 245 F (–40 to 118 C)
using Master LWT sensor
Master is lead chiller.
49
ACTION TAKEN
RESET
BY CONTROL
METHOD
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
PROBABLE
CAUSE
High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS board,
loss of condenser air, liquid
valve closed, operation
beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser air,
liquid valve closed, opera-
tion beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser air,
liquid valve closed, opera-
tion beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser air,
liquid valve closed, opera-
tion beyond capability.
High-pressure or loss-of-
charge switch open, faulty
control relay or CPCS board,
loss of condenser air, liquid
valve closed, operation
beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser air,
liquid valve closed, opera-
tion beyond capability.
High-pressure switch open,
faulty control relay or CPCS
board, loss of condenser air,
liquid valve closed, opera-
tion beyond capability.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Thermistor failure, damaged
cable/wire or wiring error.
Faulty expansion valve or
EXV board, faulty cooler suc-
tion thermistor (T5) or leav-
ing fluid thermistor (T1).
Faulty expansion valve or
EXV board, faulty cooler suc-
tion thermistor (T6) or leav-
ing fluid thermistor (T1).
Dual chiller LWT thermistor
failure, damaged cable/wire
or wiring error.