Table 16 — Configuration Mode and Sub-Mode Directory (cont)
KEYPAD
SUB-MODE
ITEM
ENTRY
OPT2
BAUD
(cont)
LOAD
LLCS
LCWT
DELY
ICE.M
RSET
CRST
ENTER
CRT1
CRT2
DGRC
HRST
HRT1
HRT2
DGRH
DMDC
DM20
SHNM
SHDL
SHTM
DLS1
DLS2
LLEN
MSSL
SLVA
LLBL
LLBD
LLDY
MARQUEE
NAVIGATOR
DISPLAY RANGE
DISPLAY RANGE
1 - 5
1 - 2
1 - 3
AUTOMATIC
CIR A LEADS
CIR B LEADS
2 - 60 ∆ F
2 - 60 ∆ F
(–16 - 16 ∆ C)
(–16 - 16 ∆ C)
0 - 15
ENBL-DSBL
ENBL-DSBL
NO RESET
4-20 INPUT
0 - 4
OUT AIR TEMP
RETURN FLUID
SPACE TEMP
0° - 125 F
0° - 125 F
(–18 - 52 C)
(–18 - 52 C)
0° - 125 F
0° - 125 F
(–18 - 52 C)
(–18 - 52 C)
–30 - 30 ∆ F
–30 - 30 ∆ F
(–17 - 17 ∆ C)
(–17 - 17 ∆ C)
0 - 4
0° - 125 F
0° - 125 F
(–18 - 52 C)
(–18 - 52 C)
0° - 125 F
0° - 125 F
(–18 - 52 C)
(–18 - 52 C)
–30 - 30 ∆ F
–30 - 30 ∆ F
(–17 - 17 ∆ C)
(–17 - 17 ∆ C)
0 - 3
0 - 100%
0 - 99
0 - 60%
0 - 120
0 - 100%
0 - 100%
ENBL-DSBL
ENBL-DSBL
SLVE-MAST
SLVE-MAST
0 - 239
ENBL-DSBL
ENBL-DSBL
40 - 400HRS
40 - 400HRS
0 - 30 MIN
0 - 30 MIN
ITEM EXPANSION
240
0
CCN BAUD RATE
4800
9600
19,200
00
38,4
EQUAL

LOADING SEQUENCE

STAGED
SELECT
LEAD/LAG CIRCUIT
SELECT
HIGH LCW ALERT
0 - 15
MINUTES OFF TIME
ICE MODE ENABLE
COOLING RESET
NO COOL RESET
FULL COOL RESET
DEGREES COOL
HEATING RESET
0 - 4
NO HEAT RESET
FULL HEAT RESET
DEGREES HEAT
RESET
DEMAND LIMIT
0 - 3
SELECT
DEMAND LIMIT
0 - 100%
AT 20 mA
LOADSHED GROUP
0 - 99
NUMBER
LOADSHED DEMAND
0 - 60%
MAXIMUM LOADSHED
0 - 120
DEMAND LIMIT
0 - 100%
SWITCH 1
DEMAND LIMIT
0 - 100%
SWITCH 2
LEAD/LAG CHILLER
ENABLE
MASTER/SLAVE
SELECT
0 - 239
SLAVE ADDRESS
LEAD/LAG BALANCE
SELECT
LEAD/LAG BALANCE
LAG START DELAY
37
COMMENT
Default: 3
1 = 2400
2 = 4800
3 = 9600
4 = 19,200
5 = 38,400
Default: 1
1 = Equal
2 = Staged
Default: 1 (Size 080-420);
2 (Size 040-070)
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 60
LIMIT
Default: 0
Default: DSBL
0 = No report
2 = 4 to 20 mA input
TYPE
3 = Return fluid
4 = Space temperature
Default: 125 F
TEMP
Default: 0° F
TEMP
Default: 0° F
RESET
Not Supported
TYPE
Not Supported
TEMP
Not Supported
TEMP
Not Supported
Default: 0
Default: 100%
Default: 0
Default: 0
DELTA
Default: 60 minutes
TIME
Default: 80%
Default: 50%
Default: DSBL
Default: Master
Default: 0
Default: DSBL
Default: 168 hours
DELTA
Default: 5 minutes