Carrier Air Conditioner Operation And Service Manual page 75

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

DESCRIPTION
1
Circuit B Analog Values
2
Percent Total Capacity
3
Percent Available Cap
4
Discharge Pressure
5
Suction Pressure
6
Saturated Condensing Tmp
Saturated Suction Temp
7
8
Compressor Suction Temp
9
Suction Superheat Temp
10
EXV % Open
DESCRIPTION
1
CIRC. B DISCRETE OUTPUTS
2
Compressor B1 Relay
3
Compressor B2 Relay
4
Compressor B3 Relay
5
Compressor B4 Relay
6
Unloader B1 Relay
7
Unloader B2 Relay
8
Liq. Line Solenoid Valve
9
Hot Gas Bypass Relay
10
11
CIRC. B DISCRETE INPUTS
12
Compressor B1 Feedback
13
Compressor B2 Feedback
14
Compressor B3 Feedback
15
Compressor B4 Feedback
16
Oil Pressure Switch B
17
Low Pressure Switch B
APPENDIX A — CCN TABLES (cont)
CIRCB_AN (Circuit B Analog Parameters)
STATUS
0-100
0-100
nnn.n
nnn.n
snnn.n
snnn.n
snnn.n
snnn.n
0-100.0
CIRCBDIO (Circuit B Discrete Parameters)
STATUS
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
OPEN/CLOSE
OPEN/CLOSE
75
UNITS
POINT
%
CAPB_T
%
CAPB_A
PSI
DP_B
PSI
SP_B
°F
TMP_SCTB
°F
TMP_SSTB
°F
CTB_TMP
^F
SH_B
%
EXV_B
UNITS
POINT
K_B1_RLY
K_B2_RLY
K_B3_RLY
K_B4_RLY
UNL_B1
UNL_B2
LLSV_B
HGB
K_B1_FBK
K_B2_FBK
K_B3_FBK
K_B4_FBK
OILSW_B
LPS_B
FORCEABLE
N
N
N
N
N
N
N
N
N
FORCEABLE
N
N
N
N
N
N
N
N
N
N
N
N
N
N

Hide quick links: