Carrier Air Conditioner Operation And Service Manual page 33

Air-cooled reciprocating liquid chillers with comfortlink controls 50/60 hz
Hide thumbs Also See for Air Conditioner:
Table of Contents

Advertisement

KEYPAD
SUB-MODE
ENTRY
UNIT
ENTER
CIR.A
ENTER
CIR.B
ENTER
SUB-MODE
KEYPAD ENTRY
PRC.A
ENTER
PRC.B
ENTER
KEYPAD
SUB-MODE
ENTRY
COOL
ENTER
HEAT
HEAD
ENTER
Table 10 — Temperature Mode and Sub-Mode Directory
ITEM
RANGE
–40 - 245 F
CEWT
(–40 - 118 C)
–40 - 245 F
CLWT
(–40 - 118 C)
–40 - 245 F
OAT
(–40 - 118 C)
–40 - 245 F
SPT
(–40 - 118 C)
CNDE
–40 - 245 F
(–40 - 118 C)
CNDL
–40 - 245 F
(–40 - 118 C)
DLWT
–40 - 245 F
(–40 - 118 C)
–40 - 245 F
SCT.A
(–40 - 118 C)
–40 - 245 F
SST.A
(–40 - 118 C)
–40 - 245 F
SGT.A
(–40 - 118 C)
–40 - 245 ∆ F
SUP.A
(–40 - 118 ∆ C)
–40 - 245 F
SCT.B
(–40 - 118 C)
–40 - 245 F
SST.B
(–40 - 118 C)
–40 - 245 F
SGT.B
(–40 - 118 C)
–40 - 245 ∆ F
SUP.B
(–40 - 118 ∆ C)
Table 11 — Pressure Mode and Sub-Mode Directory
ITEM
RANGE
0-900
DP.A
Psig
0-900
SP.A
Psig
0-900
DP.B
Psig
0-900
SP.B
Psig
Table 12 — Set Point Mode and Sub-Mode Directory
ITEM
RANGE
–20 - 70 F
CSP.1
(–29 - 21 C)
–20 - 70 F
CSP.2
(–29 - 21 C)
–20 - 32 F
CSP.3
(–29 - 0° C)
80 - 140 F
HSP.1
(27 - 60 C)
80 - 140 F
HSP.2
(27 - 60 C)
80 - 140 F
HD.P.A
(27 - 60 C)
80 - 140 F
HD.P.B
(27 - 60 C)
ITEM EXPANSION
COOLER ENTERING FLUID
COOLER LEAVING FLUID
OUTSIDE AIR TEMPERATURE
SPACE TEMPERATURE
CONDENSER ENTERING FLUID
CONDENSER LEAVING FLUID
LEAD/LAG LEAVING FLUID
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPRESSOR SUCTION GAS TEMP
SUCTION SUPERHEAT TEMP
SATURATED CONDENSING TMP
SATURATED SUCTION TEMP
COMPRESSOR SUCTION GAS TEMP
SUCTION SUPERHEAT TEMP
ITEM EXPANSION
DISCHARGE PRESSURE
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION PRESSURE
ITEM EXPANSION
COOLING SETPOINT 1
COOLING SETPOINT 2
ICE SETPOINT
HEATING SETPOINT 1
HEATING SETPOINT 2
HEAD PRESSURE SETPOINT A
HEAD PRESSURE SETPOINT B
33
COMMENT
COMMENT
Pressure is converted from SCT.A.
Pressure is converted from SST.A.
Pressure is converted from SCT.B.
Pressure is converted from SST.B.
COMMENT
Default 44 F
Default 44 F
Default 32 F
Not Supported
Not Supported
Default 113 F
Default 113 F

Hide quick links: